Specifications, Appendix – Rockwell Automation 284 ArmorStart User Manual User Manual

Page 321

Advertising
background image

Appendix

A

Specifications

Bulletin 280/281

Electrical Ratings

UL/NEMA

IEC

Power Circuit

Rated Operation Voltage

200V…575V

200…575V

Rate Insulation Voltage

600V

600 V

Rated Impulsed Voltage

6 kV

6 kV

Dielectric Withstand

2200V AC

2500V AC

Operating Frequency

50/60 Hz

50/60 Hz

Utilization Category

N/A

AC-3

Protection Against Shock

N/A

IP2X

Rated Operating Current Max.

1.2 A

2.5 A

5.5 A

16 A

Control
Circuit

Rated Operation Voltage

24V DC (+10%, -15%) A2 (should be grounded at voltage source)

120V AC (+10%, -15%) A2 (should be grounded at voltage source)

240V AC (+10%, -15%) A2 (should be grounded at voltage source)

Rate Insulation Voltage

250V

250V

Rated Impulsed Voltage

4 kV

Dielectric Withstand

1500V AC

2000V AC

Overvoltage Category

III

Operating Frequency

50/60 Hz

50/60 Hz

Short Circuit
Protection

SCPD Performance Type 1

Current Rating

Voltage

480Y/277V

480 V

600Y/347 V

600 V

0.24…1.2 A

Sym. Amps RMS

65kA

65kA

30kA

30kA

0.5…2.5 A

1.1…5.5 A

3.2…16 A

30kA

30kA

30kA

30kA

SCPD List

Size per NEC Group Motor

Power Requirements

Units

W/O HOA

W/ HOA

Control Voltage

Volts

24V DC

120V AC

240V AC

24V DC

120V AC

240V AC

Contactor (Pick Up)

Amps

0.71

0.583

0.292

0.71

0.583

0.292

Contactor (Hold In)

Amps

0.63

0.075

0.038

0.063

0.075

0.038

Total Control Power (Pick Up)

VA (W)

(17.0 W)

70

70

(21.0 W)

83

84

Total Control Power (Hold In)

VA (W)

(1.5 W)

9

9

(5.6 W)

22

23

External Devices powered by Control Voltage

Outputs (2) 1 A max. each)

Amps

2

2

2

2

2

2

Total Control (Pick Up) with

max. outputs

VA (W)

(65.0 W)

310

550

(73.0 W)

336

579

Total Control (Hold In) with

max. outputs

VA (W)

(50.0 W)

249

489

(58.0 W)

275

518

Input Ratings

Rated Operation Voltage

24V DC

Input On-State Voltage Range

10…26V DC

Input On-state Current

3.0 mA @ 10V DC

7.2 mA @ 24V DC

Input Off-state Voltage Range

0…5V DC

Input Off-state Current

<1.5 mA

Input Filter — Software Selectable

Off to On

Settable from 0…64 ms in 1 ms increments

On to Off

Settable from 0…64 ms in 1 ms increments

Input Compatibility

N/A

IEC 1+

Number of inputs

4

Sensor Source

Voltage Status Only

11…25V DC from DeviceNet™

Current Available

50 mA MAX per Input, 200 mA Total

Output Ratings (Sourced
from Control Circuit)

Rated Operation Voltage

240V AC / 30V DC

240V AC / 30V DC

Rate Insulation Voltage

250V

250V

Backplane Current Load

400 mA

50/60 Hz

50/60 Hz

Type of control circuit

Electromechanical Relay

Kind of Current

AC/DC

Conventional Thermal Current I

th

Total of both outputs

2 A

Type of Contacts

Normally Open (N.O.)

Number of Contacts

2

ArmorPoint® Ratings

Backplane Current Load

400 mA

Advertising
This manual is related to the following products: