Programming 99

H3-09 Terminal A2 Function Selection

The A2 or A3 analog input can be programmed to perform many different functions. The setting of parameter H3-09 and
H3-05 determines which of the following functions the A2 or A3 analog input will respectively perform. The level of the A2
analog input, as a percentage of the maximum input, can be viewed by the U1-16 monitor.

Function: Adds to Terminal A1
Setting: 0

By setting analog input to 0 the level of the analog input will be summed with the level of the frequency reference analog input A1.

Function: Frequency Gain
Setting: 1
Setting analog input to 1 allows the analog input to act as a gain to the frequency reference.

Fig. 68 Frequency Reference Gain

Table 20 Analog Input Functions

Parameter

Setting

Function

Control Method (A1-02)

V/f

V/f with

PG

Open

Loop

Vector

Flux

Vector

0

Adds to Terminal A1 (factory default, H3-09)

O

O

O

O

1

Frequency Reference Gain

O

O

O

O

2

Aux. Frequency Reference 1 (factory default, H3-05)

O

O

O

O

3

Aux. Frequency Reference 2

O

O

O

O

4

Output Voltage Bias

O

O

X

X

5

Accel / Decel Time Coefficient

O

O

O

O

6

DC Injection Braking Current

O

O

O

X

7

Overtorque / Undertorque Detection Level

O

O

O

O

8

Stall Prevention Level During Run

O

O

X

X

9

Frequency Reference Lower Limit

O

O

O

O

A

Jump Frequency 4

O

O

O

O

B

PID Feedback

O

O

O

O

C

PID Set Point

O

O

O

O

D

Frequency Reference Bias 2

O

O

O

O

E

Motor Temperature

O

O

O

O

10

FWD Torque Limit

X

X

O

O

11

REV Torque Limit

X

X

O

O

12

Regenerative Torque Limit

X

X

O

O

13

Torque Reference

X

X

X

O

14

Torque Compensation

X

X

X

O

15

FWD/ REV Torque Limit

X

X

O

O

1F

Not Used

O

O

O

O

1: Frequency Reference Gain

100%

-10V

10V

-100%

0V

20mA

4mA

Advertising