Programming 125

L4-05 Frequency Reference Loss Detection Selection

L4-06 Frequency Reference at Loss of Frequency Reference

Setting Range:

0.0 to 100.0% of previous frequency reference

Factory Default: 80.0% of previous frequency reference

The Drive can be configured to compensate for the loss of its external frequency reference. An external frequency reference is
considered lost if it drops 90% of its value in 400mS or less.

Fig. 90 Loss of Frequency Reference Timing Diagram

To enable Frequency loss detection, set L4-05= “1: Enabled @ % of PrevRef”. If Frequency Reference Loss Detection is
enabled and the reference is lost, the Drive continues to operate at the frequency referenced by parameter L4-06. When the
frequency reference returns, the Drive again follows the frequency reference.

Setting H2-01/H2-02= “C: Loss of Ref”, configures a digital output as a Frequency Reference Loss indication only when
L4-05= “1: Enabled @ % of PrevRef”.

L5 Fault Restart

L5-01 Number of Auto Restart Attempts

Setting Range:

0 to 10

Factory Default: 0

L5-02 Auto Restart Operation Selection

All major faults will cause the Drive to stop. For some faults it is possible to configure the Drive to attempt a restart
automatically. After the fault occurs, the Drive baseblocks for L2-03 seconds. After the baseblock is removed the Drive checks
if a fault condition still exists. If no fault condition exists the Drive will attempt to restart the motor. If the restart is

Setting

Description

0

Disabled

1

Enabled @ % of PrevRef (factory default)

Setting

Description

0

No Fault Relay (factory default)

1

Fault Relay Active

t

Frequency

Reference

Output

Frequency

t

10%

T

L4-06

100%

T = 400mS

100%

10%