F1-12 Number of PG Gear Teeth 1
F1-13 Number of PG Gear Teeth 2

Setting Range:

0 to 1000

Factory Default: 0

Parameter F1-12 and F1-13 sets the gear ratio between the motor shaft and the encoder (PG) according to the following formula:

A gear ratio of 1 will be used if either of these parameters is set to zero. This function is not available in Flux Vector control
(A1-02 = 3).

F1-14 PG Open-Circuit (PGO) Detection Time

Setting Range:

0.0 to 10.0 seconds

Factory Default: 2.0 seconds

Parameter F1-14 sets the time from when the pulse generator (PG) signal is missing to when the fault signal is displayed on the
Drive. The stopping method when a “PGO” fault is detected is selected by parameter F1-02. If a speed reference is commanded,
but the motor is physically locked, a “PGO” fault will occur even though the PG is connected to the Drive.

F2 AI-14 Setup

F2-01 AI-14 Input Selection

This parameter selects the function for channel 1, 2, and 3 when AI-14B analog input reference option board is used.
When the 3-channel individual input is used, parameter b1-01 is automatically set to “l” (frequency reference from control
circuit terminal). The option/inverter reference selection, which is selected by a multi-function contact input (H1-0x = “2”), is
disabled when using the AI-14B option.

F3 DI-08, 16 Setup

F3-01 DI-08 / DI-16H2 Input Selection

This parameter sets the function of the DI-08 or the DI-16H2 digital input option board. When o1-03 is set to 2 or higher, the
input will be BCD, and the units will change to the o1-03 setting.

Setting

Description

0

3-Channel Individual (channel 1: terminal A1, channel
2: terminal A2, channel 3: terminal A3) (factory default)

1

3-Channel Addition (Summed values of channels 1, 2,
and 3 is the frequency reference)

Setting

Description

0

BCD 1% Unit (factory default)

1

BCD 0.1% Unit

2

BCD 0.01% Unit

3

BCD 1Hz. Unit

4

BCD 0.1Hz. Unit

5

BCD 0.01Hz Unit

6

BCD (5-digit) 0.01 Hz. Unit (for DI-16H2 only)

7

Binary Input

No. of Motor RPM’s =

No. of PG Output Pulses × 60

PG Pulses/Revolution (F1-01) ×

No. of Teeth Gear 2 (F1-13)

No. of Teeth Gear 1 (F1-12)