Programming 82 – Yaskawa F7 Drive Programming Manual User Manual

Page 90

Advertising
background image

Programming 82

Function: PID SFS Cancel
Setting: 34

SFS means softstart, also referred to as accel/decel in this description.

By configuring a digital input as a PID SFS (softstart) Cancel input (H1-0x= 34), the operator will be able to use a contact closure to

remove the acceleration and deceleration times that are applied to changes in the PID setpoint by the b5-17 parameter. If the digital
input configured as PID SFS Cancel is closed, the PID setpoint Accel/Decel (Parameter b5-17) will be ignored. Immediate updating
of any change to the setpoint will apply.

Function: Input Level Selection
Setting: 35

When using the PID Function built into the Drive, the chosen set point is compared with the measured feedback. The difference is
called the Error. The proportional and integral function are applied to this error. For some applications it may be appropriate to invert
the input to the PID block. This can be accomplished by setting one of the digital inputs up as an Input Level Sel (H1-0x=35). When
an Input Level Sel digital input is closed the Error will be inverted before it is passed to the PID block.

Fig. 52 PID Error signal Inversion Block Diagram

Function: DC Injection Braking
Setting: 60

When a DC injection braking command is input while the Drive is stopped, DC injection braking operation is activated. When
a run command or a jog command is input, DC injection braking is released to start operation (jog operation has priority).

Fig. 53 DC Injection Braking Input Timing Diagram

Set

Point

+

-

Z

-1

PI Block

Feed

back

H1=0x=35

OP

CLOSED

Open

Closed

PID Block

DC Injection Braking Command

Fwd Run Command

ON

OFF

OFF

Output Frequency

ON

OFF

OFF

DC Injection

Braking

DC Injection

Braking

DC Injection Braking

Start Frequency

(B2-01)