Programming 116 – Yaskawa F7 Drive Programming Manual User Manual

Page 124

Advertising
background image

Programming 116

L1-02 Motor Overload Protection Time

Setting Range:

0.1 to 20.0 Minutes

Factory Default: 8.0 Minutes

The L1-02 parameter will set the allowed operation time before the OL1 fault will occur when the Drive is running at 60 Hz
and 133% of the motor’s full load amp rating (E2-01). Adjusting the value of L1-02 can shift the set of OL1 curves up the Y-
axis of the diagram below but will not change the shape of the curves.

Fig. 82 Motor Overload Protection Time based on Output frequency and Load

L1-03 Motor Overheat Alarm Operation Selection

L1-04 Motor Overheat Fault Operation Selection

L1-05 Motor Temperature Input Filter Time

Setting Range:

0.00 to 10.00 Seconds

Factory Default: 0.20 Seconds

The Drive can be programmed to accept a PTC (Positive Temperature Coefficient) Thermistor input for monitoring motor tem-
perature. By setting parameter H3-09= “E: Motor Temperature”, and attaching the PTC thermistor per the figure below, the
Drive can react to the increasing motor winding temperature with both an alarm (L1-03) and a fault (L1-04).

Setting

Description

0

Ramp to Stop

1

Coast to Stop

2

Fast-Stop

3

Alarm Only (factory default)

Setting

Description

0

Ramp to Stop

1

Coast to Stop (factory default)

2

Fast-Stop

125%

4

2

Time

(M

inut

es

)

Output Current

(Percent of motor FLA)

E2-01 200%

6

8

10

60Hz

10Hz

175%

150%