Programming 186

Monitor Select

o1-01

User Monitor Selection
User Monitor Sel

Selects which monitor will be displayed in the operation menu
upon power-up when o1-02 = 4.

4 to 45

6

A

A

A

A

o1-02

User Monitor Selection After
Power-Up
Power-On Monitor

Selects which monitor will be displayed upon
power-up.
1: Frequency Reference (U1-01)
2: Output Frequency (U1-02)
3: Output Current (U1-03)
4: User Monitor (set by o1-01)

1 to 4

1

A

A

A

A

o1-03

Digital Operator Display
Selection
Display Scaling

0 to

39999

0

A

A

A

A

o1-04

Setting unit for frequency
parameters related to V/F
characteristics
Display Units

Sets the setting units related to V/F pattern frequency related
parameters (E1-04, -06, -09, -11)
0: Hertz
1: RPM

0 to 1

0

-

-

-

A

o1-05

LCD Brightness Adjustment
LCD Contrast

Sets the contrast of the Digital Operator LCD. A setting of “1” is
the lightest contrast and a setting of “5” is the darkest contrast.

0 to 5

3

A

A

A

A

Denotes that parameter can be changed when the Drive is running.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

Open

Loop

Vector

Flux

Vector

Sets the units of the Frequency References (d1-01 to
d1-17), the Frequency Reference Monitors (U1-01,
U1-02, U1-05), and the Modbus communication
frequency reference.
0: Hz
1: % (100% = E1-04)
2 to 39: RPM (Enter the number of motor poles).
40 to 39999: User display.

Set the number desired at maximum

output frequency.

4 digit number
Number of digits from the right of the

decimal point

Example 1: o1-03 = 12000, will result in frequency
reference from 0.0 to 200.0 (200.0 = Fmax).
Example 2: o1-03 = 21234, will result in frequency
reference from 0.00 to 12.34 (12.34 = Fmax).