Programming 171

Digital Inputs

H1-01

Multi-Function Digital Input
Terminal S3 Function
Selection
Terminal S3 Sel

Selects the function of terminals S3 to S8.
0: 3-wire control
FWD/REV selection for 3-wire sequence.
1: Local/Remote Selection

Closed = Local, Open = Remote.

2: Option/Inv Selection

Selects source of frequency reference and sequence.
Closed = Option Card, Open = b1-01 & b1-02.

3: Multi-Step Frequency Reference 1

Based on status of Multi-Step Reference 1 to 4 (d1-16).

4: Multi-Step Frequency Reference 2

Based on status of Multi-Step Reference 1 to 4 (d1-16).

5: Multi-Step Frequency Reference 3

Based on status of Multi-Step Reference 1 to 4 (d1-16).

6: Jog Frequency Reference
Closed = frequency reference from d1-17
7: Accel/Decel Time Se1ection 1

Based on status of Accel/Decel Time Selection 1 and 2.

8: External BaseBlock N.O.
Closed = Output transistors forced off.
Open = Normal operation.
9: External BaseBlock N.C.
Closed = Normal operation.
Open = Output transistors forced off.
A: Acc/Dec Ramp Hold

Closed = Acceleration suspended and speed held.

B: External Overheat Alarm (OH2)

Closed = OH2 alarm.

C: Terminal A2 Enable

Closed = Terminal A2 is active.
Open = Terminal A2 is disabled.

D: V/F Control with PG Disabled

Closed = Speed feedback control disabled.

E: ASR Integral Reset

Closed = Integral reset.

F: Terminal Not Used

Terminal closure has no effect.

10: MOP Increase
Closed = frequency reference increases.
Open = frequency reference held.

Must be set in conjunction with MOP Decrease and b1-01
must be set to 1.

11: MOP Decrease

Closed = frequency reference decreases.

Open = frequency reference held.

Must be set in conjunction with MOP Increase and b1-01 must
be set to 1.

12: Forward Jog

Closed = Drive runs forward at frequency reference entered
into parameter d1-17.

13: Reverse Jog

Closed = Drive runs in reverse at frequency reference entered
into parameter d1-17.

14: Fault Reset

Closed = Resets the Drive after the fault and the run command
have been removed.

(Continued on following page).

0 to 78

24

A

A

A

A

H1-02

Multi-Function Digital Input
Terminal S4 Function
Selection
Terminal S4 Sel

0 to 78

14

A

A

A

A

Denotes that parameter can be changed when the Drive is running.