Programming 39, D1-17 jog frequency reference – Yaskawa F7 Drive Programming Manual User Manual

Page 47

Advertising
background image

Programming 39

If H3-05 or H3-09= “3: Aux Reference 2” then the analog input A3 or A2, respectively will be used instead of Frequency
Reference 3 for the third preset speed. If H3-05 or H3-09

≠ 3 then Frequency Reference 3 (d1-03) will be used.

Fig. 31 Preset Reference Timing Diagram

d1-17 Jog Frequency Reference

Setting Range:

0.00 to E1-04 Value

Factory Default: 6.00 Hz

IMPORTANT

The programming of d1-01 through d1-04 and d1-17 will be affected by the setting of o1-03. The programming
of these parameters will be in the units specified by Display Scaling parameter (o1-03).

Frequency

Ref

er

enc

e

FWD (REV) Run/Stop

Term.S4 (H1-02=3)

Multi-step Speed Ref. 2
Term.S5 (H1-03=4)

D1-04

20.0Hz

D1-01

5.0Hz

D1-02

10.0Hz

D1-03

15.0Hz

ON

ON

ON

ON

Multi-step Speed Ref. 3
Term.S6 (H1-04=5)

Jog Ref.
Term.S8 (H1-06=6)

ON

ON

ON

D1-05

25.0Hz

D1-06

30.0Hz

D1-07
35.0Hz

D1-17

6.0Hz

Time

D1-12

60.0Hz

D1-13

65.0Hz

D1-14
70.0Hz

D1-15

75.0Hz

D1-16
80.0Hz

ON

ON

ON

Multi-step Speed Ref. 1

Multi-step Speed Ref. 4
Term.S7 (H1-05=32)

ON

ON

ON

ON

ON