E1 v/f pattern, Programming 50 – Yaskawa F7 Drive Programming Manual User Manual

Page 58

Advertising
background image

Programming 50

E1 V/f Pattern

E1-01 Input Voltage Setting

Setting Range:

155.0V to 255.0V (240V Models)
310.0V to 510.0V (480V Models)

Factory Defaults: 240.0V (240V Models)

480.0V (480V Models)

Set the Input Voltage parameter (E1-01) to the nominal voltage of the connected AC power supply. This parameter adjusts the
levels of some protective features of the Drive (i.e. Overvoltage, Stall Prevention, etc.). E1-01 also serves as the Maximum/Base
Voltage used by the Preset V/Hz curves (E1-03= 0 to E).

E1-03 V/f Pattern Selection

The Drive operates utilizing a set V/f pattern to determine the appropriate output voltage level for each commanded speed. There
are 15 different preset V/f patterns to select from with varying voltage profiles, saturation levels (frequency at which maximum
voltage is reached), and maximum frequencies.

There are also settings for Custom V/f patterns that will allow the programmer to manually set (“Customize”) the V/f pattern
using parameters E1-04 through E1-13.

Using parameter E1-03, the programmer can select one of the preset V/f patterns or chose between a custom V/f pattern with an
upper voltage limit (E1-03= “F: Custom V/F”) and a custom V/f pattern without a voltage limit (E1-03= “FF: Custom w/o limit”).

WARNING

DRIVE INPUT VOLTAGE (NOT MOTOR VOLTAGE) MUST BE SET IN E1-01 FOR THE PROTECTIVE
FEATURES OF THE DRIVE TO FUNCTION PROPERLY. FAILURE TO DO SO MAY RESULT IN
EQUIPMENT DAMAGE AND/OR PERSONAL INJURY.

Setting

Description

0

50 Hz

1

60 Hz Saturation

2

50 Hz Saturation

3

72 Hz

4

50 Hz VT1

5

50 Hz VT2

6

60 Hz VT1

7

60 Hz VT2

8

50 Hz HST1

9

50 Hz HST2

A

60 Hz HST1

B

60 Hz HST2

C

90 Hz

D

120 Hz

E

180 Hz (not supported at this time)

F

Custom V/f (factory default, with parameter values per setting 1)

FF

Custom w/o limit

Advertising