Programming 129

L6-04 Torque Detection Selection 2

L6-05 Torque Detection Level 2

Setting Range:

0 to 300% of Drive rated output current

Factory Default: 150% of Drive rated output current

L6-06Torque Detection Time 2

Setting Range:

0.0 to 10.0 Seconds

Factory Default: 10.0 Seconds

Torque detection 2 functions the same way as torque detection selection 1. The multi-function outputs associated with torque
detection 2 are torque detection 2 N.O. and torque detection 2 N.C. (H2-0x = 18 and 19, respectively). See parameter
description above for details.

L7 Torque Limit

L7-01 Forward Torque Limit

L7-02 Reverse Torque Limit

L7-03 Forward Regenerative Torque Limit

L7-04 Reverse Regenerative Torque Limit

Setting Range:

0 to 300 %

Factory Default: 200%

The torque limit function limits the amount of motor torque in all four quadrants of vector control operation:

· Forward Motoring

· Forward Regenerating

· Reverse Motoring

· Reverse Regenerating

Setting

Description

0

Disabled (factory default)

1

OL3 at Speed Agree - Alarm

2

OL3 at Run - Alarm

3

OL3 at Speed Agree - Fault

4

OL3 at Run - Fault

5

UL3 at Speed Agree - Alarm

6

UL3 at Run - Alarm

7

UL3 at Speed Agree - Fault

8

UL3 at Run - Fault