F7 Monitor List

Table A.2 F7 Monitor List

Parameter

No.

Parameter Name

Digital Operator Display

Description

Display Units

Monitor

U1-01

Frequency Reference
Frequency Ref

Frequency reference (speed command) monitor when in
REMOTE mode, frequency reference (speed command)
setting location when in local mode or b1-01 = 0.

Set by o1-03.

U1-02

Output Frequency
Output Freq

Output frequency

Set by o1-03.

U1-03

Output Current
Output Current

Output current

0.01A

U1-04

Control Method
Control Method

Control method set in A1-02.
0 = V/F without PG
1 = V/F with PG
2 = Open Loop Vector
3 = Flux Vector

-

U1-05

Motor Speed
Motor Speed

Motor speed feedback

Set by o1-03.

U1-06

Output Voltage
Output Voltage

Output voltage

0.1Vac

U1-07

DC Bus Voltage
DC Bus Voltage

DC Bus Voltage

1Vdc

U1-08

Output Power
Output kWatts

Output power

0.1kW

U1-09

Torque Reference
Torque Reference

Torque reference

0.1%

U1-10

Input Terminal Status
Input Term Sts

Input terminal status

-

U1-11

Output Terminal Status
Output Term Sts

Output terminal status.

-

0

1: FWD. run

(Terminal S1) is ON.

1: REV. run

(Terminal S2) is ON.

1: Multi-function input 1

(Terminal S3) is ON.

1: Multi-function input 2

(Terminal S4) is ON.

1: Multi-function input 3

(Terminal S5) is ON.

1: Multi-function input 4

(Terminal S6) is ON.

1: Multi-function input 5

(Terminal S7) is ON.

1: Multi-function input 6

(Terminal S8) is ON.

0 0 0 0 0 0 0

1: Multi-function Output 1

(Terminal M1-M2) is ON.

1: Multi-function Output 2

(Terminal M3-M4) is ON.

1: Multi-function Output 3

(Terminal M5-M6) is ON.

0: Not used
1: Fault output

(Terminal MA-MB-MC) is
ON.

0 0 0 0 0 0 0 0