Programming 61

The Motor Rated Current parameter (E2-01) is used by the Drive to protect the motor and for proper Vector control when
using Open Loop Vector or Flux Vector control methods (E3-01 = 2 or 3). The motor protection parameter L1-01 is enabled by
default. Set E2-01 to the full load amps (FLA) stamped on the motor’s nameplate.
During Auto-tuning, it is required for the operator to enter the motor’s rated current (T1-04) in the Auto-Tuning menu. If the
Auto-tuning operation completes successfully (T1-02 = 0), the value entered into T1-04 will automatically be written into E4-
01.

E4-02 Motor 2 Rated Slip

Setting Range:

Model Dependent

Factory Default: Model Dependent

This parameter sets the motor rated slip frequency in units of 0.01Hz. If the rotational Auto-tuning operation completes
successfully, this value is automatically calculated. The default setting varies depending on the drive model number (o2-04).
The following equation to calculate the motor rated slip frequency based on motor nameplate data:

E4-03 Motor 2 No Load Current

Setting Range:

Model Dependent

Factory Default: Model Dependent

Set E4-03 to the motor no-load current at rated voltage and rated frequency. If the rotational Auto-tuning operation completes
successfully (T1-02 = 0), this value is automatically calculated. Consult the motor manufacturer for the proper value if the no
load current is not stated on the motor nameplate.

E4-04 Motor 2 Number of Poles

Setting Range: 2 to 48
Factory Default: 4

This parameter sets the number of motor poles. During auto-tuning, it is required for the operator to enter the number of motor
poles (T1-06) in the Auto-Tuning menu. If the Auto-tuning operation completes successfully (T1-02 = 0, 1, or 2), the value
entered into T1-06 will automatically be written into E4-04.

E4-05 Motor 2 Line-to-Line Resistance

Setting Range:

0.0000to 65.000

Ω

Factory Default: 9.842

Ω

Sets the line-to-line resistance of the motor’s stator winding. If the Auto-tuning operation completes successfully (T1-02 = 0,
1, or 2), this value is automatically calculated. Remember this value must be entered as line-line and not line neutral.

where:

fs

f

N P

(

)

120

-----------------

=

f

s

: slip frequency (Hz)

f : rated frequency (Hz)
N : rated motor speed (rpm)
P : number of motor poles

Phase-to-phase Resistance at

Insulation Class Temperature

273 + (25 + insulation class temperature) /2

273 + insulation class temperature

E2-05=

)

(

X

Where: Insulation class temperature is in

°C