B6 reference hold (dwell), Programming 23 – Yaskawa F7 Drive Programming Manual User Manual

Page 31

Advertising
background image

Programming 23

b5-16 Sleep Delay Time

Setting Range:

0.0 to 25.5 Seconds

Factory Default: 0.0 Seconds

b5-17 PID Accel/Decel Time

Setting Range: 0.0 to 25.5 Seconds
Factory Default: 0.0 Seconds

This is a soft start function that is applied to the PID setpoint analog input. Instead of having nearly instantaneous changes in
signal levels, there is a programmed ramp applied to level changes. When changing setpoints the error can be limited by
gradually ramping the setpoint through the use of parameter b5-17.

b5-18 PID Setpoint Selection

In order to use parameter b5-19 as the PID Setpoint, set parameter b5-18= “1: Enabled”. If b5-18= “0: Disabled” the PID
Setpoint will either be:

Modbus Register 06H (If Register 0FH bit 1 is high)

The active frequency reference (i.e. Determined by the setting of b1-01). See Table 1 “Setpoint Options”

b5-19 PID Setpoint Value

Setting Range:

0.00 to 100.00%

Factory Default: 0.00%

Parameter b5-19 is for a PID Setpoint value. When b5-18= “1: Enabled”, the value of b5-19 will take precedent over any other
PID setpoint unless the Drive is set up for Differential Feedback, in which case, b5-18 and b5-19 have no affect on the PID
function.

b6 Reference Hold (Dwell)

The reference hold or dwell function is used to temporarily hold the output frequency at a set reference, for a set time, and then
continue to ramp up. This function can be used when driving a permanent magnet motor, or a motor with a heavy starting load.
This pause in acceleration allows the magnets in a permanent magnet motor to synchronize with the stator field of the motor,
thus reducing traditionally high starting current.

Fig. 19 Dwell Timing Chart

Setting

Description

0

Disabled (factory default)

1

Enabled

Run command

Output frequency

Time

ON

b6-03

OFF

b6-01

b6-04

b6-02

Advertising