Programming 52

E1-05 Maximum Output Voltage

Setting Range:

0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 230.0V (240V Models)

480.0V (480V Models)

E1-06 Base Frequency

Setting Range:

0.0 to 400.0 Hz

Factory Default: 60.0 Hz

E1-07 Mid Output Frequency A

Setting Range:

0.0 to 400.0 Hz

Factory Default: 3.0 Hz

E1-08 Mid Output Voltage A

Setting Range:

0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 12.6V (240V Models)

25.2V (480V Models)

E1-09 Minimum Output Frequency

Setting Range:

0.0 to 400.0 Hz

Factory Default: 0.5 Hz

E1-10 Minimum Output Voltage

Setting Range:

0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 2.3V (240V Models)

4.6V (480V Models)

E1-11 Mid Output Frequency B

Setting Range:

0.0 to 400.0 Hz

Factory Default: 0.0 Hz

E1-12 Mid Output Voltage B
E1-13 Base Voltage

Setting Range:

0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 0.0V (240V Models)

0.0V (480V Models)

Advertising