Programming 74 – Yaskawa F7 Drive Programming Manual User Manual

Page 82

Advertising
background image

Programming 74

.

Fig. 45 Timing Diagram of Accel / Decel Time Change

Function: External Baseblock N.O.
Setting: 8

Function: External Baseblock N.C.
Setting: 9

When the Drive is commanded into baseblock, gating of the output transistor stops and output voltage/frequency drops to zero
(motor coasts). The Drive can be forced into a baseblock state by either closing a digital input configured for Ext Baseblk N.O.
(H1-0x= 8) or opening a digital input configured for Ext Baseblk N.C. (H1-0x= 9).

When the baseblock state is removed the speed search function is used to catch the coasting motor and ramp it back to the
commanded speed.

The method of speed search, Current Detection or Speed Estimation, that is utilized when the baseblock input is removed
depends on the setting of parameter b3-01:

If b3-01= “0: SpdsrchF Disable” or “1: SpdsrchF Enable”; Speed Estimation is used
If b3-01= “2: SpdsrchI Disable” or “3: SpdsrchF Enable”; Current Detection is used

Accel/decel Time Selection 1

Multi-function Input

Setting = “7”

Accel/decel Time Selection 2

Multi-function Input

Setting = “1A”

Accel Time

Decel Time

Open or not set

Open or not set

C1-01

C1-02

Closed

Open or not set

C1-03

C1-04

Open or not set

Closed

C1-05

C1-06

Closed

Closed

C1-07

C1-08

Output

Frequency

Accel Time 1

(C1-01)

Decel Time 1* (C1-02)

Accel Time 2 (C1-03)

Decel Time 2*

Decel Time 1*

Time

FWD (REV) Run Command

ON

OFF

ON

ON

Accel/Decel Time Selection 1
(Terminals S3 to S8, H1-0x = “7”)

* When “deceleration to stop” is selected (B1-03 = “0”)

(C1-04)

(C1-02)

Accel Time 3

(C1-05)

Decel Time 3* (C1-06)

Accel Time 4 (C1-07)

Decel Time 4*

Decel Time 1*

(C1-08)

(C1-02)

ON

OFF

ON

OFF

ON

Accel/Decel Time Selection 2
(Terminals S3 to S8, H1-0x = “1A”)

ON

Advertising