Programming 75

Fig. 46 External Baseblock Characteristics

Function: Acceleration/Deceleration Ramp Hold
Setting: A

The Acc/Dec Ramp Hold function will clamp (“hold”) the speed of the output frequency whenever a digital input that has been
programmed for it (H1-0x= A) is closed. All acceleration or deceleration will stop and the Drive will hold the current speed.
Once the input is opened, acceleration or deceleration continues.

The Acc/Dec Ramp Hold function is affected by parameter d4-01. If d4-01= “1: Enabled” and the Acc/Dec Ramp Hold
functions are both being used, whenever the Ramp Hold input is closed the output frequency is memorized. When interrupted
power is returned and a Run command is input, the frequency reference will be the last output frequency memorized by the
Acc/Dec Ramp Hold function, if the Acc/Dec Ramp Hold input is still closed.

Fig. 47 Accel/Dec Ramp Hold Function Timing Diagram

Function: Terminal A2 Enable
Setting: C

Any digital input configured as Term A2 Enable (H1-0x= C) when open will cause the input to analog input A2 to be ignored.
If analog input A2 is configured as the Main Reference (H3-13= “1: Main Fref TA1”), then the Term A2 Enable input will have no effect.

RUN Command

Baseblock Input

Speed Command

Output Frequency

Begin Speed Search

from stored Speed

Command

TIME

Run

Command

Hold Input

Output

Frequency

Input

Power

d4-01=1

d4-01=0

ON

ON

ON

OFF

OFF

OFF

TIME