Programming 56

E2 Motor Setup

E2-01 Motor Rated Current

Setting Range:

Model Dependent

Factory Default: Model Dependent

The Motor Rated Current parameter (E2-01) is used by the Drive to protect the motor and for proper Vector control when using
Open Loop Vector or Flux Vector control methods (A1-02 = 2 or 3). The motor protection parameter L1-01 is enabled by
default. Set E2-01 to the full load amps (FLA) stamped on the motor’s nameplate.
During Auto-tuning, it is required for the operator to enter the motor’s rated current (T1-04) in the Auto-Tuning menu. If the
Auto-tuning operation completes successfully (T1-02 = 0), the value entered into T1-04 will automatically be written into E2-
01.

E2-02 Motor Rated Slip

Setting Range:

Model Dependent

Factory Default: Model Dependent

This parameter sets the motor rated slip frequency in units of 0.01Hz. If the rotational Auto-tuning operation completes successfully,
this value is automatically calculated. The default setting varies depending on the drive model number (o2-04). The following

Table 11 V/f Pattern Default Settings for Drive Capacity 55~300kW for 240V Class (Continued)

Parameter

No.

Name

Unit

Factory Setting

E1-03

V/f Pattern Selection

8

9

A

B

C

D

E

F

E1-04

Max. Output
Frequency

Hz

50.0

50.0

60.0

60.0

90.0

120.0

180.0

60.0

E1-05

Max. Output Voltage

V

240.0

240.0

240.0

240.0

240.0

240.0

240.0

240.0

E1-06

Base
Frequency

Hz

50.0

50.0

60.0

60.0

60.0

60.0

60.0

60.0

E1-07

Mid. Output
Frequency A

V

2.5

2.5

3.0

3.0

3.0

3.0

3.0

3.0

E1-08

Mid. Output
Voltage A

V

17.2

23.0

17.2

23.0

13.8

13.8

13.8

13.8

E1-09

Min. Output
Frequency

Hz

1.3

1.3

1.5

1.5

1.5

1.5

1.5

1.5

E1-10

Mid. Output
Voltage

V

8.0

10.3

8.0

12.6

6.9

6.9

6.9

6.9

E1-11

Mid Output
Frequency B

Hz

0

0

0

0

0

0

0

0

E1-12

Mid Output
Voltage B

V

0

0

0

0

0

0

0

0

E1-13

Base Voltage

V

0

0

0

0

0

0

0

0

For 480V class units, the value is twice that of 240V class units.