Programming 34

C5-05 ASR Limit

Setting Range:

0.0 to 20.0 %

Factory Default: 5.0 %

Sets ASR frequency compensation limit as a percentage of maximum output frequency (El -04). This function is enabled when
V/f control with PG feedback is selected as the control method (A1-02).

C5-06 ASR Delay Time

Setting Range:

0.000 to 0.500 sec

Factory Default: 0.004 sec

This parameter sets the filter time constant for the time from the speed loop to the torque command output. Mechanical backlash
in an application causes secondary current (I

2

) reference variations in the motor’s rotor. This condition can prevent the adjustment

of ASR parameters. The output delay time constant is used to control these secondary current (I

2

) reference variations.

C5-07 ASR Switching Frequency

Setting Range:

0.0 to 400.0 Hz

Factory Default: 20.0 Hz

Sets frequency to change ASR proportional gain and integral time constant in units of 0.1Hz when flux vector control is selected.

Fig. 28 ASR Switching Frequency Level

Notes:

1. When C5-07 = 0, proportional gain 1 (C5-01) and integral time 1 (C5-02) are selected.

2. During V/f control with PG feedback (A1-02 = 1), the frequency switching level becomes the maximum output frequency

(E1-04).

3. The multi-function input “77: ASR Gain Switch” has priority over the ASR switch frequency (C5-07).

C5-08 ASR Integral Limit

Setting Range:

0 to 400 %

Factory Default: 400 %

Parameter C5-08 adjusts the amount of integral control of the automatic speed regulator in the Flux Vector control mode (A1-

02 = 3). Setting parameter C5-08 to zero will make the ASR control proportional. Setting C5-08 to greater than 0% will make

the ASR control proportional and sets the ASR integral upper limit as a percentage of rated torque of the connected motor.

Fig. 29 ASR Integral Limit Function

C5-07

f

FB

=

P g

ain

· I ti

me

C5-01

C5-02

C5-03

C5-04

0

P = Number of Motor Poles

N = Motor RPM

P · N

120

f

FB

Motor Speed

* When C5-07 =”0”, proportional gain 1 (C5-01)

where:

and integral time 1 (C5-02) are selected.

or

E1-04

Speed

Slip

Torque

C5-08=0

P Control

C5-08=400%

P-I Control

C5-08 > 0%