Programming 187

Key Selections

o2-01

Local/Remote Key Function
Selection
Local/Remote Key

Determines if the Digital Operator Local/Remote key is

functional.

0: Disabled

1: Enabled

0 to 1

1

A

A

A

A

o2-02

STOP Key Function
Selection
Oper STOP Key

Determines if the STOP key on the Digital Operator will stop the
Drive when Drive is operating from external terminals or serial
communication.
0: Disabled
1: Enabled

0 to 1

1

A

A

A

A

o2-03

User Parameter Default Value
User Defaults

Allows storing of parameter settings as a User Initialization
Selection.
0: No Change
1: Set Defaults - Saves current parameter settings as user

initialization. A1-03 now allows selecting <1110> for user
initialization and returns o2-03 to zero.

2: Clear All - Clears the currently saved user initialization. A1-03

no longer allows selecting <1110> and returns o2-03 to zero.

0 to 2

0

A

A

A

A

o2-04

Drive/kVA Selection
Inverter Model #

Sets the kVA of the Drive. Enter the number based on Drive model
number. Use the last four digits of the model number.
CIMR-F7U

.

This parameter only needs to be set when installing a new control
board. Do not change for any other reason. Refer to Table B.1.

0 to FF

Varies

by

kVA

A

A

A

A

o2-05

Frequency Reference Setting
Method Selection
Operator M.O.P.

Determines if the Data/Enter key must be used to input a frequency
reference from the Digital Operator.
0: Disabled - Data/Enter key must be pressed to enter a frequency

reference.

1: Enabled - Data/Enter key is not required. The frequency

reference is adjusted by the up and down arrow keys on the
Digital Operator without having to press the data/enter key.

0 to 1

0

A

A

A

A

o2-06

Operation Selection when
Digital Operator is
Disconnected
Oper Detection

Determines if the Drive will stop when the Digital Operator is
removed when in LOCAL mode or b1-02=0.
0: Disabled - The Drive will not stop when the Digital Operator is

removed.

1: Enabled - The Drive will fault (OPR) and coast to stop when the

Digital Operator is removed.

0 to 1

1

A

A

A

A

o2-07

Cumulative Operation Time
Setting
Elapsed Time Set

Sets the initial value of the elapsed operation timer U1-13.

0 to

65535

0H

A

A

A

A

o2-08

Cumulative Operation Time
Selection
Elapsed Time Run

Sets how time is accumulated for the elapsed operation timer
U1-13.
0: Power-On Time - Time accumulates when the Drive is

powered.

1: Running Time - Time accumulates only when the Drive is

running.

0 to 1

0

A

A

A

A

o2-09

Initialization Specification
Selection
Init Mode Sel

Determines parameter default values after a Drive initialization
(A1-03) is executed. This should always be set to "1" for North
American installations.
1: American spec

Possible damage to equipment or injury may occur if this setting is
changed from “1: American spec.”. o2-09 is a macro parameter
that can change the default values of terminal I/O and many other
parameters in the drive. Consult Yaskawa factory for details if
adjustment is required.

1

1

A

A

A

A

o2-10

Cumulative Cooling Fan
Operation Time Setting
Fan ON Time Set

Sets the initial value of the heatsink fan operation time monitor
U1-40.

0 to

65535

0H

A

A

A

A

o2-12

Fault Trace/Fault History
Clear Function
FLT Trace Init

Clears the fault memory contained in the U2 and U3 monitors.
0: Disabled - no effect
1: Enabled - resets U2 and U3 monitors, and returns o2-12 to zero.

0 to 1

0

A

A

A

A

o2-14

kWh User Monitor
Initialization
kWH MonitorClear

Used to reset the kilowatt-hour monitor U1-29 to zero.
0: Disabled - no change
1: Enabled - Resets U1-29 to zero and returns o2-14 to zero.

0 to 1

0

A

A

A

A

Denotes that parameter can be changed when the Drive is running.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

Open

Loop

Vector

Flux

Vector

WARNING