480vac – Yaskawa F7 Drive Programming Manual User Manual

Page 7

Advertising
background image

v

480Vac

Table i.3 480Vac Drive Specifications

Model Number CIMR-F7U

40P4

40P7

41P5

42P2

43P7

44P0

45P5

47P5

4011

4015

4018

4022

Rated output capacity

(kVA)

1.4

1.6

2.8

4.0

5.8

6.6

9.5

13.0

18.0

24.0

30.0

34.0

Horsepower

*2

0.5/0.75

1

1.5/2

3

5

-

7.5

10

15

20

25

30

Rated output current

(A)

1.8

2.1

3.7

5.3

7.6

8.7

12.5

17.0

24.0

31.0

39.0

45.0

Overload capacity

*3

(% of rated output
current for 60 sec.)

150

Current limit

*2

(% of

rated output current)

150

Carrier frequency

*4

2kHz

Maximum output
frequency

300.0Hz

Rated output capacity (kVA)

1.4

1.6

2.8

4.0

5.8

6.6

9.5

13.0

21.0

26.0

30.0

38.0

Horsepower

*2

0.5/0.75

1

1.5/2

3

5

-

7.5

10

15/20

25

30

30

Rated output current (A)

1.8

2.1

3.7

5.3

7.6

8.7

12.5

17.0

27.0

34.0

40.0

50.4

Overload capacity

*3

(% of rated output
current for 60 sec.)

120

120

120

120

120

120

120

120

107

109

117

107

Current limit (% of
rated output current)

120

Carrier frequency (kHz)

*5

15

15

15

15

15

15

15

15

8

10

10

10

Maximum output
frequency

400.0Hz

Maximum output voltage

3-phase; 380, 400, 415, 440, 460, or 480Vac (Proportional to input voltage)

Model Number CIMR-F7U 4030

4037

4045

4055

4075

4090

4110

4132

4160

4185

4220

4300

Rated output capacity

(kVA)

46.0

57.0

69.0

85.0

110.0

140.0

160.0

200.0

230.0

280.0

N/A

Horsepower

*2

40

50

60

75

100

125/150

-

200

250

300

Rated output current

(A)

60.0

75.0

91.0

112.0

150.0

180.0

216.0

260.0

304.0

370.0

Overload capacity

*3

(% of rated output
current for 60 sec.)

150

Current Limit (% of
rated output current)

150

Carrier frequency

*4

2kHz

Maximum output
frequency

300.0Hz

Rated output capacity

(kVA)

51.0

59.0

73.0

95.0

120.0

140.0

180.0

200.0

230.0

315.0

390.0

510.0

Horsepower

*2

40/50

60

75

100

125

150

200

-

250

300/350 400/450

500+

Rated output current

(A)

67.2

77.0

96.0

125.0

156.0

180.0

240.0

260.0

304.0

414.0

515.0

675.0

Overload capacity

*3

(% of rated output
current for 60 sec.)

107

117

114

108

115

120

108

120

120

107

118

120

Current Limit (% of
rated output current)

120

Carrier frequency (kHz)

*5

8

8

8

5

5

8

5

5

5

2

2

2

Maximum output
frequency

400.0Hz

Maximum output voltage

3-phase, 380, 400, 415, 440, 460 or 480Vac (Proportional to input voltage)

*1 The difference between Heavy Duty ratings and the Normal Duty ratings for the Drive are the rated input and output current, overload capacity, carrier frequency, current limit, and

maximum output frequency. Parameter C6-01 must be set to value of “0” for Heavy Duty ratings and “2” for Normal Duty ratings. Factory default is Heavy Duty (C6-01=0).

*2 Horsepower ratings are based on 230V or 460V NEC Table 430.150. The maximum applicable motor output is given for a standard 4-pole motor. When selecting the actual motor

and Drive, be sure that the Drive's rated output current is appropriate for the motor's rated current.

*3 Models 2110, 4220, 4300 have an overload rating of 120% of rated output current for 60 seconds.

*4 2kHz is the Maximum carrier frequency value and default carrier frequency value for all models.

*5 Each value shown is the Maximum carrier frequency and default carrier frequency.

O

utp

ut rat

ings

Heavy Du

ty

*1

Norma

l Duty

*1

O

utpu

t rat

ing

s

Heavy Dut

y

*1

No

rm

al Du

ty

*1

Advertising