Programming 62

E4-06 Motor 2 Leakage Inductance

Setting Range:

0.0 to 40.0 %

Factory Default: Model Dependent

Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. If the rotational Auto-tuning
operation completes successfully (T1-02 = 0), this value is automatically calculated.

E4-07 Motor Rated Output

Setting Range:

0.00 to 650.00 kW

Factory Default: Model Dependent

This parameter sets the motor rated power in kilowatts (kW). If the rotational Auto-tuning operation completes successfully

(T1-02 = 0), this value is automatically calculated.

F1 PG Option Setup

F1-01 PG Pulses / Revolution

Setting Range:

0 to 60000

Factory Default: 1024

This parameter sets the number of PG pulses per one revolution of the encoder (pulse generator) when using PG option board

on the Drive.

F1-02 Operation Selection at PG Open Circuit (PGO)

This parameter sets the stopping method when a PG open circuit fault (PGO) occurs according to the PGO detection time set in

parameter F1-14.

F1-03 Operation Selection at Overspeed (OS)

This parameter sets the stopping method when a overspeed fault (OS) occurs according to the OS detection level and detection

time set in parameter F1-08 and F1-09, respectively.

Setting

Description

0

Ramp to Stop - Decelerate to stop using active deceleration time.

1

Coast to Stop (factory default)

2

Fast-stop - Decelerate to stop using the deceleration time in C1-09.

3

Alarm Only - Drive continues operation.

Setting

Description

0

Ramp to Stop - Decelerate to stop using active deceleration time.

1

Coast to Stop (factory default)

2

Fast-stop - Decelerate to stop using the deceleration time in C1-09.

3

Alarm Only - Drive continues operation.