Programming 166

Motor Setup

E2-01

Motor Rated Current
Motor Rated FLA

Set to the motor nameplate full load current in amperes (A). This
value is automatically set during Auto-Tuning.

Varies

by

kVA

Varies

by

kVA

Q

Q

Q

Q

E2-02

Motor Rated Slip
Motor Rated Slip

Set to the motor rated slip in hertz (Hz).
This value is automatically set during rotational Auto-Tuning.

Varies

by

kVA

Varies

by

kVA

A

A

A

A

E2-03

Motor No-Load Current
No-Load Current

Set to the magnetizing current of the motor as a percentage of full
load amps (E2-01). This value is automatically set during rotational
Auto-Tuning.

Varies

by

kVA

Varies

by

kVA

A

A

A

A

E2-04

Number of Motor Poles
Number of Poles

Set to the number of motor poles.
This value is automatically set during Auto-Tuning.

2 to 48

4

-

Q

-

Q

E2-05

Motor Line-to-Line
Resistance
Term Resistance

Set to the phase-to-phase motor resistance in ohms (

Ω).

This value is automatically set by Auto-Tuning.

0.000 to

65.000

Varies

by

kVA

A

A

A

A

E2-06

Motor Leakage Inductance
Leak Inductance

Set to the voltage drop due to motor leakage inductance as a
percentage of motor rated voltage.
This value is automatically set during Auto-Tuning.

0.0 to

40.0%

Varies

by

kVA

-

-

A

A

E2-07

Motor Iron-core Saturation
Coefficient 1
Saturation Comp 1

Set to the motor iron saturation coefficient at 50% of magnetic
flux.
This value is automatically set during rotational Auto-Tuning.

0.00 to

0.50

0.50

-

-

A

A

E2-08

Motor Iron-core Saturation
Coefficient 2
Saturation Comp 2

Set to the motor iron saturation coefficient at 75% of magnetic
flux.
This value is automatically set during rotational Auto-Tuning.

0.50 to

0.75

0.75

-

-

A

A

E2-09

Motor Mechanical Loss
Mechanical Loss

Set to the motor mechanical loss as a percentage of motor rated
power (kW) capacity.
Adjust in the following circumstances:

• When torque loss is large due to motor bearing friction.

• When the torque loss in the load is large.

0.0 to

10.0

0.0%

-

-

A

A

E2-10

Motor Iron Loss for Torque
Compensation
Tcomp Iron Loss

Set to the motor iron loss in watts (W).

0 to

65535 W

Varies

by

kVA

A

A

-

-

E2-11

Motor Rated Output
Mtr Rated Power

Set to the motor rated power in kilowatts (kW).
This value is automatically set during Auto-Tuning.
1HP = 0.746kW

0.00 to
650.00

kW

Varies

by

kVA

Q

Q

Q

Q

Denotes that parameter can be changed when the Drive is running.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

Open

Loop

Vector

Flux

Vector