Programming 131

L8 Hardware Protection

L8-01 Internal Dynamic Braking Resistor Protection Selection

This parameter selects the dynamic braking resistor protection only when using the 3% duty cycle heatsink mount Yaskawa
braking resistor. This parameter does not enable or disable the general dynamic braking function of the Drive. Do not adjust
this parameter when using any other braking resistors.

Fig. 96 Heat Sink Mount Resistor

L8-02 Overheat Pre-Alarm Level

Setting Range:

50 to 130

o

C

Factory Default: 95

o

C

L8-03 Overheat Pre-Alarm Operation Selection

The Drive is capable of warning the operator of an impending heatsink over-temperature fault via an OH pre-alarm. The level
at which the pre-alarm will activate is determined by the setting of parameter L8-02. Measurement of the heatsink temperature

Setting

Description

0

Not Provided (factory default)

1

Provided

Setting

Description

0

Ramp to Stop (Decel Time C1-02)

1

Coast to Stop

2

Fast-Stop (Decel Time C1-09)

3

Alarm Only (factory default)