Programming 175, Table a.1 f7 parameter list (continued) – Yaskawa F7 Drive Programming Manual User Manual

Page 183

Advertising
background image

Programming 175

H2-02

Terminal M3-M4 Function
Selection
Term M3-M4 Sel

11: Reset Command Active
Closed = When the Drive receives a reset command from a

digital input terminal or serial communication.

12: Timer Output
Output for independent timer, controlled by b4-01 and b4-02.

Used in conjunction with the digital input H1-

= 18 “timer

function”.

13: Fref/Fout Agree 2
Closed = When Drive output frequency equals the frequency

reference +/- the hysteresis of L4-04.

14: Fref/Set Agree 2
Closed = When the Drive output frequency and the frequency

reference are equal to the value in L4-03 +/- the hysteresis of
L4-04.

15: Frequency Detection 3
Closed = When the Drive output frequency is less than or equal

to the value in L4-03 with the hysteresis determined by L4-04.

16: Frequency Detection 4
Closed = When the Drive output speed is greater than or equal

to the value in L4-03, with the hysteresis determined by L4-04.

17: Torque Detection 1 N.C.
Open = When the output current/torque exceeds the value set

in parameter L6-02 for more time than is set in parameter
L6-03.

18: Torque Detection 2 N.O.
Closed = When the output current/torque exceeds the value set

in parameter L6-05 for more time than is set in parameter
L6-06.

19: Torque Detection 2 N.C.
Open = when the output current/torque exceeds the value set in

parameter L6-05 for more time than is set in parameter L6-06.

1A: Reverse Direction
Closed = When the Drive is running in the reverse direction.
1B: Baseblock 2 N.C.
Open = When Drive is not outputting voltage.
1C: Motor 2 Selection
Closed = When motor 2 is selected by multi-function input

“motor 2 selection”.

1D: Regenerating
Closed = When in regenerating mode.
1E: Restart Enabled
Closed = When the Drive is performing an automatic restart

attempt. Automatic restart is configured by parameter L5-01.

1F: Overload (OL1)
Closed = When OL1 function is at 90% of its trip point or

greater.

20: OH Prealarm
Closed = When the Drive’s heatsink temperature exceeds the

setting of parameter L8-02.

30: During Torque Limit (when in speed control)
Closed = When in torque limit.
31: During Speed Limit
Closed = When in speed limit.
32: During Speed Limit (when in torque control)
Closed = When motor frequency is at the speed limit value

when running in torque control.

33: Zero-Servo Complete
Closed = When Zero Servo is complete within the b9-02 zero

servo completion width.

37: During Run 2
Closed = When Drive is operating (except during baseblock or

DC braking).

38: Drive Enable
Closed = When the Drive enable input is active.

0 to 38

1

A

A

A

A

H2-03

Terminal M5-M6 Function
Selection
Term M5-M6 Sel

0 to 38

2

A

A

A

A

Denotes that parameter can be changed when the Drive is running.

Note: Some digital outputs are control method dependent.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

Open

Loop

Vector

Flux

Vector