Programming 60

E3-05 Motor 2 Mid Output Frequency A

Setting Range:

0.0 to 400.0 Hz

Factory Default: 3.0 Hz

E3-06 Motor 2 Mid Output Voltage VA

Setting Range:

0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 12.6V (240V Models)

25.2V (480V Models)

E3-07 Motor 2 Minimum Output Frequency

Setting Range:

0.0 to 400.0 Hz

Factory Default: 0.5 Hz

E3-08 Motor 2 Minimum Output Voltage

Setting Range:

0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 2.3V (240V Models)

4.6V (480V Models)

Fig. 40 Motor 2 V/f Curve

To set V/f characteristics in a straight line, set the same values for E3-05 and E3-07. In this case, the setting for E3-06 will be

disregarded. Be sure that the four frequencies are set in the following manner or else an OPE10 fault will occur:

E4 Motor Setup 2

E4-01 Motor 2 Rated Current

Setting Range:

Model Dependent

Factory Default: Model Dependent

Output voltage (V)

Frequency (Hz)

E3-07 E3-05 E3-04 E3-02

E3-03

E3-06

E3-08

E3-07

≤ E3-05 < E3-04 ≤ E3-02