Programming 133

L8-10 Heatsink Cooling Fan Operation Selection

L8-11 Heatsink Cooling Fan Operation Delay Time

Setting Range:

0 to 300 Seconds

Factory Default: 300 Seconds

Parameters L8-10 and L8-11 allow the Drive programmer to customize the heatsink cooling fan operation. Parameter L8-10
determines whether the cooling fans are always ON whenever the Drive is powered (L8-10= “1: Fan Always On”) or if the
cooling fans are only ON when the Drive is in a Run condition (L8-10= “0: Fan On-Run Mode”).

Parameter L8-11 is a delayed OFF for the cooling fan if L8-10= “0: Fan On-Run Mode”. When the cooling fans are set to turn
OFF when the Run command is removed, parameter L8-11 will cause the fans to continue cooling the Drive for the amount of
time programmed into L8-11 after the Run command is actually removed. The Drive can be programmed to allow the cooling
fan to run for up to 5 minutes (factory default) after the run command is removed.

Both parameters are intended to extend fan life while still providing sufficient cooling for proper Drive operation.

Fig. 97 Heatsink Cooling Fan Operation Timing Diagram

L8-12 Ambient Temperature Setting

Setting Range:

113 to 140

o

F (45 to 60

o

C)

Factory Default: 113

o

F (45

o

C)

Set parameter L8-12 to the temperature

o

F (

o

C) of the area in which the Drive is mounted. If L8-12 exceeds the actual rated

ambient temperature of the Drive 113

o

F (45

o

C), the OL2 fault level will be de-rated as shown in the figure below. This will

allow the user to trade-off lighter drive loading for operation in a higher ambient temperature.

Fig. 98 Ambient Temperature Derating Curve

Setting

Description

0

Fan On-Run Mode (factory default)

1

Fan Always On

t

t

Run

Command

Heatsink Fan

RUN

L8-11

ON (CLOSED)
OFF (OPEN)

OFF (OPEN)

ON (CLOSED)

TIME

0

80%

100%

45

o

C

60

o

C

Ambient Temp.

(L8-12)

OL2 Rating

OL2 Fault Level

113

o

F

(45

o

C)

(60

o

C)

140

o

F

Advertising