Programming 24

b6-01 Dwell Reference at Start

Setting Range:

0.0 to 400.0 Hz

Factory Default:0.0 Hz

Sets the dwell frequency reference during acceleration in units of 0.1 Hz.

b6-02 Dwell Time at Start

Setting Range:

0.0 to 10.0 Seconds

Factory Default:0.0 Seconds

Sets the amount of time that the frequency reference dwells during acceleration in units of 0.1 seconds.

b6-03 Dwell Reference at Stop

Setting Range:

0.0 to 400.0 Hz

Factory Default:0.0 Hz

Sets the dwell frequency reference during deceleration in units of 0.1 Hz.

b6-04 Dwell Time at Stop

Setting Range:

0.0 to 10.0 Seconds

Factory Default:0.0 Seconds

Sets the amount of time that the frequency reference dwells during deceleration in units of 0.1 seconds.

b7 Droop Control

The droop control function reduces the motor speed based on the load torque of the motor.

b7-01 Droop Control Level

Setting Range:

0.0 to 100.0%

Factory Default:0.0%

Sets the amount of speed reduction as a percentage of maximum output frequency E1-04 when the motor is producing 100% of
rated torque. The actual amount of motor speed reduction is based on the ratio of the amount of motor torque and the maximum
output frequency E1-04.

b7-02 Droop Control Delay Time

Setting Range:

0.03 to 2.00 Seconds

Factory Default:0.05 Seconds

Sets the response time in response to load changes. Decreasing this setting will cause the response to become quicker; however,
instability may occur.