Programming 136 – Yaskawa F7 Drive Programming Manual User Manual

Page 144

Advertising
background image

Programming 136

Parameter n3-01 sets the amount of frequency reduction that will be applied in order to create the increase motor slip condition and
lower the DC Bus voltage. Normally this parameter will not need to be adjusted from the factory default. If the OV fault occurs during
HSB increase n3-01 in small increments (~2% per adjustment). n3-01 is set as a percentage of the maximum frequency (E1-04).

n3-02 High-Slip Braking Current Limit

Setting Range:

100 to 200% of Drive rated output current

Factory Default: 150% of Drive rated output current

Parameter n3-02 sets the maximum current to be output during an HSB stop. The higher n3-02 is set the shorter the motor
stopping time will be but the greater the motor winding heating will be. Increasing the setting of n3-02 should only be done in
small increments. Parameter n3-02 is set as a percentage of motor rated current (E2-01).

n3-03 High-Slip Braking Dwell Time at Stop

Setting Range:

0.0 to 10.0 Seconds

Factory Default: 1.0 Seconds

At the end of a HSB action the Drive will hold the frequency reference at the minimum frequency (E1-09) for a period of time
configured by parameter n3-03. If n3-03 is set too short there may be residual motion of the motor shaft after the HSB braking
has completed and the Drive output is shut off. The residual motion can be caused by machine/load inertia.

n3-04 High-Slip Braking Overload Time

Setting Range:

30 to 1200 Seconds

Factory Default: 40 Seconds

The OL7 (HSB Overload) fault will occur if the Drive frequency does not change within the time specified by the n3-04 parameter. The
non-changing frequency can be caused by a load with excessive inertia or a motor that is being overhauled by the load. A good test for the
excessive load inertia is whether the Drive can stop the load normally (w/o a braking resistor but not with HSB) in 180 seconds or less.

Fig. 99 High Slip Braking Timing Diagram

Run

Command

Approx. 90% of

overvoltage trip

HSB Off

HSB On

Drive will not restart until HSB stop is complete
and run command re-cycled

Motor

Speed

Output

Current

DC

Voltage

N3-02

HSB Current

N3-03

HSB Stop Dwell

E1-09

Minimum Frequency

L2-03

Minimum Baseblock

t

HSB On

HSB

Command

Motor

Speed

TIME