Programming 57

equation to calculate the motor rated slip frequency based on motor nameplate data:

E2-03 No Load Current

Setting Range:

Model Dependent

Factory Default: Model Dependent

Set E2-03 to the motor no-load current at rated voltage and rated frequency. If the rotational Auto-tuning operation completes
successfully (T1-02 = 0), this value is automatically calculated. Consult the motor manufacturer for the proper value if the no
load current is not stated on the motor nameplate.

E2-04 Number of Motor Poles

Setting Range: 2 to 48
Factory Default: 4

This parameter sets the number of motor poles. During auto-tuning, it is required for the operator to enter the number of motor
poles (T1-06) in the Auto-Tuning menu. If the Auto-tuning operation completes successfully (T1-02 = 0, 1, or 2), the value
entered into T1-06 will automatically be written into E2-04.

E2-05 Motor Line-to-Line Resistance

Setting Range:

0.0000to 65.000

Ω

Factory Default: 9.842

Ω

Sets the line-to-line resistance of the motor’s stator winding. If the Auto-tuning operation completes successfully (T1-02 = 0, 1,
or 2), this value is automatically calculated. Remember this value must be entered as line-line and not line neutral.

E2-06 Motor Leakage Inductance

Setting Range:

0.0 to 40.0 %

Factory Default: Model Dependent

Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. If the rotational Auto-tuning
operation completes successfully (T1-02 = 0), this value is automatically calculated.

E2-07 Motor Iron-core Saturation Coefficient 1

Setting Range:

0.00 to 0.50

Factory Default: 0.50

This parameter sets the motor iron saturation coefficient at 50% of the magnetic flux. If the rotational Auto-tuning operation
completes successfully (T1-02 = 0), this value is automatically calculated.

where:

fs

f

N P

(

)

120

-----------------

=

f

s

: slip frequency (Hz)

f : rated frequency (Hz)
N : rated motor speed (rpm)
P : number of motor poles

Phase-to-phase Resistance at

Insulation Class Temperature

273 + (25 + insulation class temperature) /2

273 + insulation class temperature

E2-05=

)

(

X

Where: Insulation class temperature is in

°C