Programming 167, V/f pattern 2, Motor setup 2 – Yaskawa F7 Drive Programming Manual User Manual

Page 175: Table a.1 f7 parameter list (continued)

Advertising
background image

Programming 167

V/F Pattern 2

E3-01

Motor 2 Control Method
Selection
Control Method

0: V/F control
1: V/F control with PG
2: Open-loop vector control
3: Flux vector control

0 to 3

2

A

A

A

A

E3-02

Motor 2 Maximum Output
Frequency
Max Frequency

To set V/F characteristics in a straight line, set the same values for
E3-05 and E3-07. In this case, the setting for E3-06 will be
disregarded. Be sure that the four frequencies are set in the
following manner or else an OPE10 fault will occur:
E3-02

≥ E3-04 ≥ E3-05 ≥ E3-07

Varies

by

Duty

Rating*

60.0Hz

A

A

A

A

E3-03

Motor 2 Maximum Output
Voltage
Max Voltage

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

230.0V

or

460.0V

A

A

A

A

E3-04

Motor 2 Base Frequency
Base Frequency

0.0 to
400.0

60.0Hz

A

A

A

A

E3-05

Motor 2 Mid Output
Frequency
Mid Frequency

0.0 to
400.0

3.0Hz

A

A

A

-

E3-06

Motor 2 Mid Output Voltage
VA
Mid Voltage

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

12.6

Vac

A

A

A

-

E3-07

Motor 2 Minimum Output
Frequency
Min Frequency

0.0 to
400.0

0.5Hz

A

A

A

A

E3-08

Motor 2 Minimum Output
Voltage
Min Voltage

0.0 to
255.0

(240V)

0.0 to
510.0

(480V)

2.3Vac

A

A

A

-

Motor Setup 2

E4-01

Motor 2 Rated Current
Motor Rated FLA

Set to the motor 2 nameplate full load current in amperes (A).
This value is automatically set during Auto-Tuning.

Varies

by

kVA

Varies

by

kVA

A

A

A

A

E4-02

Motor 2 Rated Slip
Motor Rated Slip

Set to the rated slip of motor 2 in hertz (Hz).
This value is automatically set during rotational Auto-Tuning.

Varies

by

kVA

Varies

by

kVA

A

A

A

A

E4-03

Motor 2 No-Load Current
No-Load Current

Set to the magnetizing current of motor 2 in percentage of full load
current (E4-01). This value is automatically set during rotational
Auto-Tuning.

Varies

by

kVA

Varies

by

kVA

A

A

A

A

E4-04

Motor 2 Number of Poles
Number of Poles

Set to the number of poles of motor 2.
This value is automatically set during Auto-Tuning.

2 to 48

4

-

A

-

A

E4-05

Motor 2 Line-to-Line
Resistance
Term Resistance

Set to the phase-to-phase resistance of motor 2 in ohms (

Ω

)

.

This value is automatically set by the Auto-Tuning.

0.000 to

65.000

Varies

by

kVA

A

A

A

A

E4-06

Motor 2 Leakage Inductance
Leak Inductance

Set to the voltage drop due to motor leakage inductance as a
percentage of rated voltage of motor 2.
This value is automatically set during Auto-Tuning.

0.0 to

40.0%

Varies

by

kVA

-

-

A

A

E4-07

Motor 2 Rated Output
Mtr Rated Power

Set to the rated power of motor 2 in kilowatts (kW).
This value is automatically set during Auto-Tuning.

0.00 to
650.00

kW

Varies

by

kVA

A

A

A

A

Denotes that parameter can be changed when the Drive is running.

* For Heavy Duty (HD) Rating: Setting Range=40.0 to 300.0. For Normal Duty (ND) Rating: Setting Range=40.0 to 400.0.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

Open

Loop

Vector

Flux

Vector

Output voltage (V)

Frequency (Hz)

E3-07 E3-05 E3-04 E3-02

E3-03

E3-06

E3-08