Programming 158

Reference Hold (Dwell)

b6-01

Dwell Reference at Start
Dwell Ref @Start

Temporarily holds the frequency reference.

0.0 to
400.0

0.0Hz

A

A

A

A

b6-02

Dwell Time at Start
Dwell Time @Start

0.0 to

10.0

0.0sec

A

A

A

A

b6-03

Dwell Frequency at Stop
Dwell Ref @Stop

0.0 to
400.0

0.0Hz

A

A

A

A

b6-04

Dwell Time at Stop
Dwell Time @Stop

0.0 to

10.0

0.0sec

A

A

A

A

Droop Control

b7-01

Droop Control Level
Droop Quantity

Sets the speed decrease as a percentage of motor base speed
(E1-06) when the motor is at 100% load torque. Setting of 0.0
disables droop control.

0.0 to
100.0

0.0%

-

-

-

A

b7-02

Droop Control Delay Time
Droop Delay Time

Determines the droop control delay time in response to a load
change.

0.03 to

2.00

0.05sec

-

-

-

A

Energy Saving

b8-01

Energy Saving Control
Selection
Energy Save Sel

Energy Savings function enable/disable selection.
0: Disabled
1: Enabled

0 to 1

0

A

A

A

A

b8-02

Energy Saving Gain
Energy Save Gain

Sets energy savings control gain when in vector control method.

0.0 to

10.0

1.0

-

-

A

A

b8-03

Energy Saving Control Filter
Time Constant
Energy Saving F.T

Sets energy saving control filter time constant when in vector
control method.

0.00 to

10.00

Varies

by

kVA

-

-

A

A

b8-04

Energy Saving Coefficient
Value
Energy Save COEF

Used to fine-tune the energy savings function when in V/F control
method.

0.0 to

655.00

Varies

by

kVA

A

A

-

-

b8-05

Power Detection Filter Time
kW Filter Time

0 to

2000

20ms

A

A

-

-

b8-06

Search Operation Voltage
Limit
Search V Limit

0 to 100

0%

A

A

-

-

Zero Servo

b9-01

Zero Servo Gain
Zero Servo Gain

Sets the position loop gain for Zero Servo command.
This function is effective when multi-function input “zero
servo command” is set.

0 to 100

5

-

-

-

A

b9-02

Zero Servo Completion
Width
Zero Servo Count

Sets number of pulses used for the multi-function output of
“zero servo completion”.

0 to

16383

10

pulses

-

-

-

A

Denotes that parameter can be changed when the Drive is running.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

Open

Loop

Vector

Flux

Vector

Run command

Output frequency

Time

ON

b6-03

OFF

b6-01

b6-04

b6-02