Yaskawa F7 Drive Programming Manual User Manual

Page 35

Advertising
background image

Programming 27

C1-07 Acceleration Time 4
C1-08 Deceleration Time 4

Setting Range:

0.0 to 6000.0 Seconds

Factory Default: 10.0 Seconds
Note: Setting range may be 0.00 to 600.00 or 0.0 to 6000.0 depending on the setting of parameter C1-10.

Acceleration time sets the time necessary for the output frequency to accelerate from 0Hz to maximum output frequency (E1-
04). Deceleration time sets the time necessary for the output frequency to decelerate from the maximum output frequency (E1-
04) to 0Hz.

C1-01 and C1-02 are the factory default active accel/decel “pair”. Other accel/decel pairs (C1-03 to C1-08) exist that can be
activated by a multi-function digital input (H1-0x= 7 and 1A). Alternatively, the active accel/decel pair can be switched from
accel/decel pair 1 (C1-01 and C1-02) to accel/decel pair 4 (C1-07 and C1-08) by a switch over frequency as programmed in
parameter C1-11.

Fig. 20 Timing Diagram of Accel / Decel Time Change

When any of the multi-function contact input selections (H1-01 to H1-06) are set to “7”and “1A”, up to four accel/decel
times can then be selected by opening or closing the appropriate accel/decel time selection commands (terminals 3 to 8).
.

Accel/decel Time Selection 1

Multi-function Input

Setting = “7”

Accel/decel Time Selection 2

Multi-function Input

Setting = “1A”

Accel Time

Decel Time

Open or not set

Open or not set

C1-01

C1-02

Closed

Open or not set

C1-03

C1-04

Open or not set

Closed

C1-05

C1-06

Closed

Closed

C1-07

C1-08

Output

Frequency

Accel Time 1

(C1-01)

Decel Time 1* (C1-02)

Accel Time 2 (C1-03)

Decel Time 2*

Decel Time 1*

Time

FWD (REV) Run Command

ON

OFF

ON

ON

Accel/Decel Time Selection 1
(Terminals S3 to S8, H1-0x = “7”)

* When “deceleration to stop” is selected (B1-03 = “0”)

(C1-04)

(C1-02)

Accel Time 3

(C1-05)

Decel Time 3* (C1-06)

Accel Time 4 (C1-07)

Decel Time 4*

Decel Time 1*

(C1-08)

(C1-02)

ON

OFF

ON

OFF

ON

Accel/Decel Time Selection 2
(Terminals S3 to S8, H1-0x = “1A”)

ON