Programming 101

Function: Stall Prevention Level
Setting: 8

Stall prevention level allows the analog input to change the stall prevention level during run (L3-06) as a percentage of the set
value. Either the analog input stall prevention level or L3-06 setting, whichever is lower, becomes effective.

Fig. 70 Stall Prevention Level

Function: Reference Lower Limit
Setting: 9

Reference lower limit allows the analog input to adjust the frequency lower limit level as a percentage of maximum output frequency
(E1-04). This works in conjunction with frequency reference lower limit d2-02. Either the analog input reference lower limit level or
d2-02 setting, whichever is greater, becomes effective.

Function: Jump Frequency
Setting: A

Jump Frequency allows the analog input to set a fourth jump frequency level in addition to jump frequency 1, 2, and 3 (d3-01,
d3-02, and d3-03, respectively) as a percentage of maximum output frequency (E1-04).

Function: PID Feedback
Setting: B

Configuring the analog input as PID feedback is a requirement of setting the Drive up for PID operation. The analog input is
the only source for feedback for PID operation though the setpoint can come from a number of different sources. Refer to the
section covering the PID parameters for more information regarding specifying the setpoint source.

Analog input gain and bias for terminals A2 (H3-10 and H3-11) and A3 (H3-06 and H3-07) can be used to configure the
analog input to match the signal from the Feedback Transmitter.

The U1-24 monitor (PID Feedback) can be used to check the PID Feedback level with the digital operator.

Function: PID Set Point
Setting: C

Setting the analog input to PID set point allows the analog input level to be the PID set point as a percentage of maximum
output frequency (E1-04). The frequency reference selected in parameter b1-01 no long becomes the PID set point.

Function: Frequency Bias 2
Setting: D

By setting the analog input to frequency bias 2, a bias signal to the active frequency reference set via A1, A2, or A3.

100%

-10V

10V

0

30%

3V

· Stall Prevention Level (setting: “8”)