Programming 51, E1-04 maximum output frequency – Yaskawa F7 Drive Programming Manual User Manual

Page 59

Advertising
background image

Programming 51

If one of the custom V/f patterns is selected, then parameters E1-04 through E1-13 will determine the V/f pattern.

E1-04 Maximum Output Frequency

Setting Range:

0.0 to 400.0 Hz

Factory Default: 60.0 Hz

Table 8 Preset V/f Patterns

Specifications

E1-03

V/f Pattern *1

Specifications

E1-03

V/f Pattern *1

General-pu

rpose

50Hz

0

Hig

h Starting Torque *2

50Hz

High

Starting

Torque 1

8

High

Starting

Torque 2

9

60Hz Saturation

1
F

60Hz

High

Starting

Torque 1

A

50Hz Saturation

2

High

Starting

Torque 2

B

72Hz

3

High Sp

eed

Operation

90Hz

C

Variable Torque

50Hz

Variable

Torque 1

4

120Hz

D

Variable

Torque 2

5

60Hz

Variable

Torque 1

6

Variable

Torque 2

7

IMPORTANT

When a factory Initialization is performed, the setting of E1-03 is unaffected but the settings of E1-04 through
E1-13 are returned to their factory default settings.

(Hz)

(V)

230

17
10

0 1.3 2.5

50

0

230

(V)

28

22

15

13

(Hz)

0 1.3 2.5

50

9

8

(Hz)

0 1.5 3.0

50 60

17
10

2

1
F

(V)

230

230

(V)

28

22

17

13

(Hz)

0 1.5 3.0

B

A

60

(Hz)

0 1.5 3.0

60 72

17
10

3

(V)

230

(Hz)

0 1.5 3.0

60 90

17
10

C

(V)

230

230

(V)

57
40

10

9

(Hz)

0 1.3

25

50

5

4

(Hz)

0 1.5 3.0

60 120

17
10

D

(V)

230

230

(V)

57
40

10

9

(Hz)

0 1.5

30

60

7

6