F4 AO-08, 12 Setup

F4-01 AO-08 / AO-12 Channel 1 Monitor Selection

Setting Range:

1 to 45

Factory Default: 2

This parameter sets the number of the monitor item to be output (U1-0x) for channel 1 of the AO-08 or AO-12 analog output

option board. The following settings cannot be set:

4, 10 to 14, 25, 28, 29, 31, 34, 39, 40, 41.

F4-02 AO-08 / AO-12 Channel 1 Gain

Setting Range:

0.0 to 1000.0 %

Factory Default: 100.0 %

This parameter sets the gain for channel 1 of the AO-08 or AO-12 analog output option board.

Example: Set F4-02 = 50 % to output 100% at 5.0 Volts.

F4-03 AO-08 / AO-12 Channel 2 Monitor Selection

Setting Range:

1 to 45

Factory Default: 2

This parameter sets the number of the monitor item to be output (U1-xx) for channel 2 of the AO-08 or AO-12 analog output

option board. The following settings cannot be set:

4, 10 to 14, 25, 28, 29, 31, 34, 39, 40, 41.

F4-04 AO-08 / AO-12 Channel 2 Gain

Setting Range:

0.0 to 1000.0 %

Factory Default: 100.0 %

This parameter sets the gain for channel 2 of the AO-08 or AO-12 analog output option board.

Example: Set F4-02 = 50 % to output 100% at 5.0 Volts.

F4-05 AO-08 / AO-12 Channel 1 Output Bias

F4-06 AO-08 / AO-12 Channel 2 Output Bias

Setting Range:

-110.0 to 110.0 %

Factory Default: 0.0 %

Parameters F4-05 and F4-06 respectively set channel 1 and channel 2 bias of the AO-08 or AO-12 analog output option board.

Example: Set F4-05 = 50% to output 0% at 5.0V output.

F4-07 AO-12 Channel 1 Signal Level

F4-08 AO-12 Channel 2 Signal Level

Parameters F4-07 and F4-08 respectively set channel 1 and channel 2 signal level of the AO-12 analog output option board.