Yaskawa F7 Drive Programming Manual User Manual

Page 71

Advertising
background image

Programming 63

F1-04 Operation Selection at Speed Deviation (DEV)

This parameter sets the stopping method when a speed deviation fault (DEV) occurs according to the OS detection level and

detection time set in parameter F1-08 and F1-09, respectively.

F1-05 PG Rotation Selection

This parameter sets the relationship between motor rotation direction and PG polarity. The motor rotation direction applies

when viewing the motor shaft from the load side.

F1-05 PG Division Rate

Setting Range:

1 to 132

Factory Default: 1

This parameter sets the division ratio for the pulse monitor of the PG-B2 encoder feedback option board. This function is not

available with the PG-X2 option board.

Division Ratio = (1 + n) / m

where n = 0 to 1 and m = 1 to 32

The first digit of the value of F1-06 stands for n, the second and the third digit stand for m (from left to right).

The possible division ratio settings are:

F1-07 Integral Function During Accel / Decel Selection

This parameter enables or disables the speed control (ASR) integral operation during acceleration or deceleration.

F1-08 Overspeed Detection Level

Setting Range:

0 to 120 %

Factory Default: 115 %

Setting

Description

0

Ramp to Stop - Decelerate to stop using active deceleration time.

1

Coast to Stop

2

Fast-stop - Decelerate to stop using the deceleration time in C1-09.

3

Alarm Only - Drive continues operation. (factory default)

Setting

Description

0

Forward = Counter Clock-wise - Phase A leads with forward run command. (factory default)

1

Forward = Clock-wise - Phase B leads with forward run command.

Setting

Description

0

Disable - Integral function is not used during accel or decel. (factory default)

1

Enable - Integral function is used at all times.

F1-05 = 1 16

n = 1

m = 16

Division Ratio = (1 + 1) / 16 = 0.125

Example:

1/32

≤ F1-06 ≤ 1