Programming 113, H5-06 drive transit wait time, H5-07 rts control selection – Yaskawa F7 Drive Programming Manual User Manual

Page 121

Advertising
background image

Programming 113

H5-06 Drive Transit Wait Time

Setting Range:

5 to 65 ms

Factory Default: 5 ms

Parameter H5-06 will set the delay time between the receiving of a message from the master and the sending of a response from
the Drive back to the master. Drive power should be cycled after a change is made to this parameter.

Fig. 81 Message Spacing

H5-07 RTS Control Selection

RTS or Request To Send control is a method of flow control applied to messaging in serial communications. Parameter H5-07
configures whether the Drive will implement RTS messaging all the time (H5-07= “0: Disabled”) or only when sending (H5-
07= “1: Enabled”). It is recommended to set H5-07= “0: Disabled”, when using RS-485 and set H5-07= “1: Enabled”, when
using RS-422. Drive power should be cycled after a change is made to this parameter.

Setting

Description

0

Disabled (RTS is always on)

1

Enabled (RTS turns on only when sending) (factory default)

PLC to Drive

Drive to PLC

PLC to Drive

Command message

Response message

Command message

Time (Seconds)

24 bits long

5 ms min.

H5-06
setting

24 bits long