Programming 168

PG Option Setup

F1-01

PG Parameter
PG Pulses/Rev

Sets the number of pulses per revolution (PPM) of the encoder
(pulse generator).

0 to

60000

1024

-

Q

-

Q

F1-02

Operation Selection at PG
Open Circuit (PGO)
PG Fdbk Loss Sel

Sets stopping method when a PG open circuit fault (PGO) occurs.
See parameter F1-14.

0: Ramp to stop - Decelerate to stop using the active deceleration

time.

1: Coast to stop
2: Fast - Stop - Decelerate to stop using the deceleration time in

C1-09.

3: Alarm Only - Drive continues operation.

0 to 3

1

-

A

-

A

F1-03

Operation Selection at
Overspeed (OS)
PG Overspeed Sel

Sets the stopping method when an overspeed (OS) fault occurs. See
F1-08 and F1-09.

0: Ramp to stop - Decelerate to stop using the active deceleration

time.

1: Coast to stop
2: Fast - Stop - Decelerate to stop using the deceleration time in

C1-09.

3: Alarm Only - Drive continues operation.

0 to 3

1

-

A

-

A

F1-04

Operation Selection at
Deviation
PG Deviation Sel

Sets the stopping method when a speed deviation (DEV) fault
occurs. See F1-10 and F1-11.

0: Ramp to stop - Decelerate to stop using the active deceleration

time.

1: Coast to stop
2: Fast - Stop - Decelerate to stop using the deceleration time in

C1-09.

3: Alarm Only - Drive continues operation.

0 to 3

3

-

A

-

A

F1-05

PG Rotation Selection
PG Rotation Sel

0: Fwd=C.C.W. - Phase A leads with forward run command.

(Phase B leads with reverse run command.)

1: Fwd=C.W. - Phase B leads with forward run command. (Phase

A leads with reverse run command.)

0 to 1

0

-

A

-

A

F1-06

PG Division Rate (PG Pulse
Monitor)
PG Output Ratio

Sets the division ratio for the pulse monitor of the PG-B2 encoder
feedback option board. This function is not available with the
PG-X2 option board.
Division ratio = (1+ n) /m (n=0 to 1, m=1 to 32)
The first digit of the value of F1-06 stands for n, the second and the
third stand for m. (from left to right).
The possible division ratio settings are:

1/32

F1-06

1

1 to 132

1

-

A

-

A

F1-07

Integral function during
accel/decel selection
PG Ramp PI/I Sel

Sets integral control during acceleration/deceleration to either
enabled or disabled.

0: Disabled - The integral function is not used while accelerating

or decelerating.

1: Enabled - The integral function is used at all times.

0 to 1

0

-

A

-

-

F1-08

Overspeed detection level
PG Overspd Level

Configures the overspeed fault (OS) detection.
OS fault will occur, if the motor speed feedback is greater than the
F1-08 setting for a time longer than F1-09. F1-08 is set as a
percentage of the maximum output frequency (E1-04). See F1-03.

0 to 120

115%

-

A

-

A

F1-09

Overspeed detection delay
time
PG Overspd Time

0.0 to

2.0

0.0 sec

-

A

-

A

F1-10

Excessive speed deviation
detection level
PG Deviate Level

Configures the speed deviation fault (DEV) detection.
DEV fault will occur if the speed deviation is greater than the
F1-10 setting for a time longer than F1-11. F1-10 is set as a
percentage of the maximum output frequency (E1-04).
Speed deviation is the difference between actual motor speed and
the frequency reference command. See F1-04.

0 to 50

10%

-

A

-

A

F1-11

Excessive speed deviation
detection delay time
PG Deviate Time

0.0 to

10.0

0.5 sec

-

A

-

A