A2 user parameters, Programming 5 – Yaskawa F7 Drive Programming Manual User Manual

Page 13

Advertising
background image

Programming 5

Fig. 1 2 & 3-Wire Control Wiring Examples

A1-00

Language Selection

E1-03

V/f Pattern Selection

o2-04

kVA Selection

o2-09

Initialization Specification Selection

A1-04 Password Entry

Setting Range:

0 to 9999

Factory Default: 0

If parameters A1-01 through A1-03 and all of the A2 parameters are locked (unchangeable) they can be unlocked by entering the
correct password number into A1-04.

Once the correct password number is entered and the specified parameters are unlocked, a 2-Wire or 3-Wire initialization will
reset the password to 0000.

A1-05 Select Password

Setting Range:

0 to 9999

Factory Default: 0

When the value set into A1-04 does NOT match the value set into A1-05, parameters A1-01 thru A1-03 and A2-32 cannot be
changed. All other parameters determined by A1-01 can be changed. Parameter A1-05 can be accessed by displaying parameter
A1-04, then press and hold the RESET key along with the MENU key simultaneously.

A2 User Parameters

A2-01 - A2-32 User Parameter

Setting Range:

b1-01 to o3-02

Factory Default: <none>

IMPORTANT

Some parameters are unaffected by either the 2-Wire or 3-Wire initialization. The following parameters will
not be reset when parameter A1-03=2220 or 3330:

S1

S2

SN

FWD Run/Stop

REV Run/Stop

2-wire control

Stop
switch
(NC contact)

Operation
switch
(NO contact)

Run command (run on momentary close)

Stop command (stop on momentary open)

Forward/reverse command (multi-function input)

Sequence input common

S5

3-wire control

2-wire control

FWD/REV