Programming 89 – Yaskawa F7 Drive Programming Manual User Manual

Page 97

Advertising
background image

Programming 89

Function: Frequency Detect 1
Setting: 4

A “Freq Detect 1” output will be closed whenever the output frequency is equal to or below the value of the programmed
Speed Agree Level (L4-01). The Speed Agree Width (L4-02) is the hysteresis to the Freq Detect 1 function. Whenever the
output frequency approaches the Speed Agree Level while accelerating it will need to be equal to or exceed the Speed Agree
Level (L4-01) plus the Speed Agree Width (L4-02) before the Freq Detect 1 output will energize.

As the output frequency approaches the Speed Agree Level while decelerating, the Freq Detect 1 output will de-energize
exactly at the Speed Agree Level.

The Freq Detect 1 function is effective during both forward and reverse operation.

Fig. 57 Freq Detect 1 Timing Diagram

Function: Frequency Detect 2
Setting: 5

A Freq Detect 2 output will be closed whenever the output frequency is equal to or above the value of the programmed Speed Agree
Level (L4-01). The Speed Agree Width (L4-02) is the hysteresis to the Freq Detect 2 function. Whenever the output frequency
approaches the Speed Agree Level (L4-01) while accelerating it will de-energize exactly at the Speed Agree Level.

As the output frequency approaches the Speed Agree Level while decelerating, the Freq Detect 2 output will
de-energize when the output frequency is equal to or below the Speed Agree Level (L4-01) minus the Speed Agree Width (L4-
02).

The Freq Detect 2 function is effective during both forward and reverse operation.

Fig. 58 Freq Detect 2 Timing Diagram

Function: Inverter Ready
Setting: 6

The Inverter Ready output will be closed whenever the Drive is not in a fault state and not being programmed. If b1-08 = “1:
Enabled”, a Drive that is in an active Run state that is also being programmed will have the Inverter Ready output closed.
Function: DC Bus Undervoltage
Setting: 7

Frequency

Detection Signal

Output

Frequency

t

a

a

- Detection Width (L4-02)

L4-01

Detection 1 Signal

ON (CLOSED)

OFF(OPEN)

a - Speed Agree Width (L4-02)

a

t

TIME

Frequency Detection Signal

Output Frequency

t

a

- Detection Width (L4-02)

a

L4-01

t

a - Speed Agree Width (L4-02)

Frequency Detection 2 Signal

a

OFF(OPEN)

ON (CLOSED)

TIME

Advertising