Programming 174, Digital outputs, Table a.1 f7 parameter list (continued) – Yaskawa F7 Drive Programming Manual User Manual

Page 182

Advertising
background image

Programming 174

Digital Outputs

H2-01

Terminal M1-M2 Function
Selection
Term M1-M2 Sel

Selects the function of terminals M1 to M6.
0: During RUN 1
Closed = When a run command is input or the Drive is

outputting voltage.

1: Zero Speed
Closed = When Drive output frequency is less than minimum

output frequency (E1-09).

2: Fref/Fout Agree 1
Closed = When Drive output frequency equals the frequency

reference +/- the hysteresis of L4-02.

3: Fref/Set Agree 1
Closed = When the Drive output frequency and the frequency

reference are equal to the value in L4-01+/- the hysteresis of

L4-02.

4: Frequency Detection 1
Closed = When the Drive output frequency is less than or equal

to the value in L4-01 with hysteresis determined by L4-02.

5: Frequency Detection 2
Closed = When the Drive output frequency is greater than or

equal to the value in L4-01, with hysteresis determined by

L4-02.

6: Inverter Ready
Closed = When the Drive is powered up, not in a fault state, and

in the DRIVE mode.

7: DC Bus Undervoltage
Closed = When the DC bus voltage falls below the UV trip

level set in L2-05.

8: Base Block 1 N.O.
Closed = When the Drive is not outputting voltage.
9: Option Reference
Closed = When the frequency reference is coming from the

Digital Operator.

A: LOCAL/REMOTE Operation
Closed = When the run command is coming from the Digital

Operator.

B: Torque Detection 1 N.O.
Closed = When the output current/torque exceeds the torque

value set in parameter L6-02 for more time than is set in
parameter L6-03.

C: Loss of Reference
Closed = When the Drive has detected a loss of the analog
frequency reference. Frequency reference is considered lost

when it drops 90% in 0.4 seconds. Parameter L4-05 determines
Drive reaction to a loss of frequency reference.

D: Braking Resistor Fault
Closed = When braking resistor or transistor is overheating or

has faulted. Only active when L8-01 = 1.

E: Fault
Closed = When the Drive experiences a major fault.
F: Not Used
10:Minor Fault - Alarm
Closed = When Drive experiences an alarm.

(Continued on following page)

0 to 38

0

A

A

A

A

Denotes that parameter can be changed when the Drive is running.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

Open

Loop

Vector

Flux

Vector