Programming 178, Analog outputs, Table a.1 f7 parameter list (continued) – Yaskawa F7 Drive Programming Manual User Manual

Page 186

Advertising
background image

Programming 178

Analog Outputs

H4-01

Terminal FM Monitor
Selection
Terminal FM Sel

Selects which monitor will be output on terminals FM and FC.
1: Frequency Reference
100% = Maximum output frequency E1-04.
2: Output Frequency
100% = Maximum output frequency E1-04.
3: Output Current
100% = Drive rated current.
5: Motor Speed
100% = Maximum output frequency E1-04.
6: Output Voltage
100% = 200/400Vac depending on Drive voltage rating.
7: DC Bus Voltage
100% = 400/800Vdc depending on Drive voltage rating.
8: Output kWatts
100% = Drive rated power.
9: Torque Reference
100% = Motor rated torque.
15:Terminal A1 Input Level
100% = 10Vdc
16:Terminal A2 Input Level
100% = 10Vdc or 20mA
17:Terminal A3 Input Level
100% = 10Vdc
18:Motor Secondary Current
100% = Motor rated secondary current.
19:Motor Excitation Current
100% = Motor rated magnetizing current.
20:SFS Output
100% = Maximum output frequency E1-04.
21:ASR Input
100% = Maximum output frequency E1-04.
22:ASR Output
100% = Maximum output frequency E1-04.
24:PID Feedback
100% = Maximum output frequency E1-04.
26:Output Voltage Reference Vq
100% = E1-05, default 240V or 480V.
27:Output Voltage Reference Vd
100% = E1-05, default 240V or 480V.
31:Not Used
32:ACR q Output (100% = Motor rated secondary current)
33:ACR d Output (100% = Motor rated magnetizing current)
36:PID Input
100% = Maximum output frequency E1-04.
37:PID Output
100% = Maximum output frequency E1-04.
38:PID Setpoint
100% = Maximum output frequency E1-04.
44:ASR Output Without Filter
45:Feedforward Control Output
100% = Motor rated secondary current.

1 to 45

2

A

A

A

A

H4-02

Terminal FM Gain Setting
Terminal FM Gain

Sets terminal FM output level when selected monitor is at 100%.

0.0 to

1000.0

100.0%

Q

Q

Q

Q

H4-03

Terminal FM Bias Setting
Terminal FM Bias

Sets terminal FM output level when selected monitor is at 0%.

–110.0 to

110.0

0.0%

A

A

A

A

H4-04

Terminal AM Monitor Selec-
tion Terminal AM Sel

Selects which monitor will be the output on terminals AM and FC.
Same function choices as H4-01.

1 to 53

3

A

A

A

A

H4-05

Terminal AM Gain Setting
Terminal AM Gain

Sets terminal AM output voltage (in percent of 10Vdc) when
selected monitor is at 100% output.

0.0 to

1000.0

50.0%

Q

Q

Q

Q

H4-06

Terminal AM Bias Setting
Terminal AM Bias

Sets terminal AM output voltage (in percent of 10Vdc) when
selected monitor is at 0% output.

–110.0 to

110.0

0.0%

A

A

A

A

H4-07

Terminal FM Signal Level
Selection
AO Level Select 1

Selects the signal level of terminal FM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*

0 or 2

0

A

A

A

A

H4-08

Terminal AM Signal Level
Selection
AO Level Select 2

Selects the signal level of terminal AM.
0: 0 to 10Vdc
1: -10 to +10Vdc
2: 4 to 20mA*

0 or 2

0

A

A

A

A

Denotes that parameter can be changed when the Drive is running. Note: Some analog outputs are control method dependent.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

Open

Loop

Vector

Flux

Vector