Programming 11

b1-04 Reverse Operation Selection

For some applications reverse motor rotation is not applicable and may even cause problems (e.g., air handling units,
pumps, etc.). Setting parameter b1-04 to 1 will cause the Drive to ignore any inputs for reverse operation. Setting parameter b1-04
to 2 will change the motor shaft rotation when a Forward Run command is given by exchanging the order of the output phasing.

The factory default setting of parameter b1-04 is “0: Reverse Enabled”. When b1-04= “1: Disabled”, reverse operation is prohibited and
no exchanging of output phasing occurs.

b1-05 Minimum Output Frequency (E1-09) or Less Operation Selection

During flux vector control (A1-02 = 3), select an operation mode to be employed when the frequency reference (analog input) drops
below the minimum output frequency (El -09). During V/f or open loop vector control, Drive output to the motor is shut off (baseblock)
when the output frequency drops below the minimum output frequency (El -09).

b1-06 Digital Input Scan Time

This parameter selects the microprocessor scan time for reading multi-function digital inputs (terminals S1 to S8). Set this parameter to
“0: 2ms” for quick response and “1: 5ms” for noisy environments.

b1-07 Local/Remote Run Selection

When the Drive is switched between the Local mode (the digital operator) to the Remote mode (determined by b1-01 and b1-02), there
is the possibility that a Run command is already present (i.e. a switch closure between S1 and SN when b1-02= “1: Terminals”).
Parameter b1-07 determines whether the Drive will:

Setting

Description

0

Reverse Enabled (factory default)

1

Reverse Disabled

2

Exchange Phase (N/A if A1-02 = 1 or 3)

Setting

Description

0

Operates According to Frequency Reference (factory default)

1

Output Shuts Off

2

Operates According to E1-09

3

Zero Speed

Setting

Description

0

2ms - For 2 Scans

1

5ms - For 2 Scans (factory default)

Setting

Description

0

Cycle Extern Run (factory default)

1

Accept Extrn Run