Programming 15

Fig. 10 Speed Search (Estimated Speed Method) after momentary power loss where the power loss

time is less than the minimum baseblock time

Fig. 11 Speed Search (Estimated Speed Method) after momentary power loss where the power loss

time exceeds the minimum baseblock time

Current Detection Method (b3-01=2 or 3): The current detection method starts searching from a predetermined frequency
while monitoring the Drive output current to determine when the rotor speed and the Drive output speed (frequency) match.
The current detection version is not bi-directional. To enable current detection Speed Search at start set b3-01= “3: SpdscrhI
enable” and program any digital input equal to Speed Search 1 (H1-0x= 61) or Speed Search 2 (H1-0x= 62). Speed Search 1
will start searching from the max. frequency (E1-04) and ramp down to meet the rotor speed. Speed Search 2 will start
searching from the set frequency and ramp down to meet the rotor speed.

IMPORTANT

If a UV1 fault occurs when current detection Speed Search is attempted, increase the setting of L2-04

IMPORTANT

If an OC fault occurs when Speed Search is attempted after power loss recovery, increase the setting of L2-03.

AC power supply

Output frequency

Output current

OFF

ON

Start using
speed detected

Set frequency
reference

Minimum baseblock time (L2-03) x 0.75*1

10 ms

*1 Baseblock time may be reduced by the output frequency
immediately before the baseblock.
*2 After AC power supply recovery, motor waits for the
minimum Speed Search Wait Time (b3-05).

*2

Minimum baseblock time (L2-03) x 0.75 *1

the motor waits for the

AC power supply

Output frequency

Output current

OFF

ON

Start using speed detected

Set frequency
reference

Minimum baseblock time
(L2-03)

10 ms

Speed Search Wait Time
(b3-05)

Note: If the frequency immediately before the baseblock is low or the power supply break time is long,
operation may be the same as the search in case 1.

Note: If the frequency immediately before the baseblock is low or the power supply off time is long,
operation may be the same as the search in case 1.