Programming 190, Table a.2 f7 monitor list (continued) – Yaskawa F7 Drive Programming Manual User Manual

Page 198

Advertising
background image

Programming 190

U1-12

Drive Operation Status
Int Ctl Sts 1

Internal Drive status

-

U1-13

Cumulative Operation Time
Elapsed Time

Total operating or power-on time of the Drive.

1hr

U1-14

Software Number
FLASH ID

Last 5 digits of the Drive's software number.

-

U1-15

Terminal A1 Input Voltage
Term A1 Level

Input voltage on Terminal A1, as a percentage of

±

10Vdc.

0.1%

U1-16

Terminal A2 Input Voltage
Term A2 level

Displays the input current (or voltage) on Terminal A2, as a
percentage of

±

10Vdc.

0.1%

U1-17

Terminal A3 Input Voltage
Term A3 level

Input voltage on Terminal A3, as a percentage of

±

10Vdc.

0.1%

U1-18

Motor Secondary Current (I

q

)

Mot SEC Current

Current being used by the motor to produce torque (I

q

).

0.1%

U1-19

Motor Excitation Current (I

d

)

Mot EXC Current

Current being used by the motor for excitation (I

d

).

0.1%

U1-20

Output Frequency After Soft Start
SFS Output

Frequency reference (speed command) after the accel and
decel ramps and S-curve.

0.01Hz

U1-21

ASR Input
ASR Input

Input error to the speed control loop (ASR).

The maximum output frequency E1-04 corresponds to 100%.

0.01%

U1-22

ASR Output
ASR Output

Output from the speed control loop (ASR).

The motor rated secondary current corresponds to 100%.

0.01%

U1-24

PI Feedback Value
PID Feedback

Feedback signal level when PID control is used.

0.01%

U1-25

DI-16H2 Input Status
DI-16 Reference

Reference value from a DI-16H2 Digital Reference Card.
The value will be displayed in binary or BCD depending on
user constant F3-01.

Set by F3-01

U1-26

Output voltage reference (Vq)

Voltage Ref (Vq)

Internal voltage reference for motor secondary current control.

0.1Vac

U1-27

Output voltage reference (Vd)

Voltage Ref (Vd)

Internal voltage reference for motor excitation current control.

0.1Vac

U1-28

CPU Number
CPU ID

Control board hardware revision.

-

U1-29

kWh
kWh Lo 4 Digits

Accumulated kilowatt-hours.

0.1kWh

U1-30

MWh
kWh Hi 5 Digits

Accumulated megawatt-hours.

1MWh

U1-32

ACR output of q axis

ACR(q) Output

Current control output value for the motor secondary current.

0.1%

U1-33

ACR output of d axis

ACR(d) Output

Current control output value for the motor excitation current.

0.1%

U1-34

First Parameter Causing an OPE
OPE Detected

Parameter number causing an "OPE" fault.

-

U1-35

Zero Servo Pulse Count

Zero Servo Pulse

Number of PG pulses times 4 for the movement range when
stopped at zero servo.

1 pulse

U1-36

PID Input
PID Input

Input error to the PID regulator
(PID Setpoint - PID Feedback).

0.01%

U1-37

PID Output
PID Output

Output of the PID regulator as a percentage of maximum
frequency (E1-04).

0.01%

Table A.2 F7 Monitor List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Display Units

1: During running
1: During zero speed
1: During reverse
1: During reset signal input
1: During speed agree
1: Drive operation ready
1: During fault detection

(Minor fault)

1: During fault detection

(Major fault)

0 0 0 0 0 0 0 0