F1-09 Overspeed Detection Delay Time

Setting Range:

0.0 to 2.0 seconds

Factory Default: 0.0 seconds

Parameter F1-08 sets the motor overspeed detection level as a percentage of maximum output frequency (E1-04) for the

overspeed fault (OS). Parameter F1-09 sets the elapsed time from when an overspeed condition is detected to when a fault

occurs. See figure below.

.

Fig. 41 Overspeed Detection Timing Diagram

A fault signal is output to stop operation after the absolute value of the motor speed exceeds the set
value of F1-08 and after the time set to F1-09 elapses. The stopping method is set by F1-03.
When parameter A1-02 = 1 (V/f with PG) the factory default setting will be 1.0. When parameter A1-02 = 3 (Flux Vector) the
factory setting will be 0.0.

F1-10 Excessive Speed Deviation Detection Level

Setting Range:

0 to 50 %

Factory Default: 10 %

F1-11 Excessive Speed Deviation Detection Delay Time

Setting Range:

0.0 to 10.0 seconds

Factory Default: 0.5 seconds

Parameter F1-10 sets the speed deviation detection level as a percentage of maximum output frequency (E1-04) for the speed
deviation fault (DEV). Parameter F1-11 sets the elapsed time from when an speed deviation condition is detected to when a
fault occurs. See figure below.

Fig. 42 Speed Deviation Detection Timing Diagram

A fault signal is output to stop operation after the deviation between speed reference and the motor speed exceeds the set value
of F1-10 and after the time set to F1-11 elapses. The stopping method is set by F1-04. Also, detection is not activated while
accelerating/decelerating or during torque control.

Overspeed Level (F1-08)

OFF

ON

|

Motor Speed

|

F1-09

Overspeed Fault Signal

0

Speed Reference

OFF

ON

Motor Speed

F1-10

Speed Deviation

Fault Signal

F1-11