Programming 107

The analog output level will correspond to the output voltage level of the Drive. 100% will be equivalent to either 200Vac or
400Vac depending on the input voltage rating of the Drive.

Function: DC Bus Voltage
Setting: 7

The analog output level will correspond to the voltage level of the Drive’s DC Bus. 100% will correspond to 400Vdc for the
240Vac input Drive and 800Vdc for the 480Vac input Drive.

Function: Output kWatts
Setting: 8

The analog output level will correspond to an internally calculated output power level based on the measured output current
and output voltage. 100% will correspond to the kilowatt rating of the Drive as determined by o2-04.

Function: Torque Reference
Setting: 9

The analog output level will correspond to the torque reference. 100% will correspond to the Drive’s rated power as
determined by o2-04.

Function: Terminal A1 Level
Setting: 15

The analog output level will correspond to the analog input to the Drive’s A1 terminal. 100% will be equivalent to 10Vdc.

Function: Terminal A2 Level
Setting: 16

The analog output level will correspond to the analog input to the Drive’s A2 terminal. 100% will be equivalent to 10Vdc or
20mA.

Function: Terminal A3 Level
Setting: 17

The analog output level will correspond to the analog input to the Drive’s A3 terminal. 100% will be equivalent to 10Vdc.

Function: Motor SEC Current
Setting: 18

The analog output level will correspond to the calculated secondary (torque producing) current. 100% will be equivalent to
motor’s full load secondary current as calculated by:

Function: Mot EXC Current
Setting: 19

The analog output level will correspond to the calculated motor excitation (magnetizing) current. 100% will be equivalent to
motor rated magnetizing current.

I sec =

Ι

Nameplate

2

- I

no load

2

=

(E2-01)

2

- (E2-03)

2