Programming 19, B5-01 pid function setting, Fig. 16 pid block diagram – Yaskawa F7 Drive Programming Manual User Manual

Page 27

Advertising
background image

Programming 19

Derivative - D
Overshoot refers to a control loop tendency to overcompensate for an error condition, causing a new error in the opposite direction.
Derivative action provides an anticipatory function that exerts a “braking” action on the control loop. When combined, the proportional
integral, and derivative actions provide quick response to error, close adherence to the setpoint, and control stability.

The analog feedback to the Drive for the PID control is via the A2 or A3 terminal. Set parameter H3-09 or H3-05 to “B: PID
Feedback” to use terminal A2 or A3, respectively, as feedback for the PID functionality of the Drive. To use the analog input
terminal A2 or A3 as the PID setpoint, set parameter H3-09 or H3-05 to “C: PID Setpoint,” respectively. The PID setpoint can
be configured to come from one of many different inputs or parameters. The table below describes the options for originating
the PID setpoint.

Fig. 16 PID Block Diagram

b5-01 PID Function Setting

The Drive can be used as a stand-alone PID controller. If PID functionality is selected by parameter b5-01, the Drive will adjust
its output to cause the feedback from a transmitter to match the PID setpoint (b5-19). To enable PID control, set b5-01 to 1, 2, 3,
or 4 according to the application.

Setting

Description

0

Disabled (factory default)

1

D = Feedback

2

D = Feed-Forward

3

Frequency Reference + PID Output (D = Feedback)

4

Frequency Reference +PID Output (D = Feed-Forward)

Terminal A1/A2

Communication

Option Card

Pulse Input

D1-01
D1-02
D1-03

.
.
.

D1-17

B1-01 = 4

3
2
1
0

B5-17

PID Accel/Decel Time

Memobus Register 0006H

PID Setpoint

Pulse Input

Memobus register

000FH bit 1 = 1

H6-02 = 2

H3-05/H3-09 = C

Terminal A2/A3

B5-18 = 1

B5-19

PID Setpoint

Pulse Input

H6-02 = 1

H3-05/H3-09

= B

Terminal A2/A3

z

-1

+

-

B5-05

PID D Time

B5-01 = 2,4

+

+

+

-

B5-02

PID P Gain

-1

PID I Time

1

B5-03

+

+

B5-04

PID I Limit

z

-1

PID Integral

Hold multi-

function input

closed

PID Integral
Reset multi-

function input

closed

Input Level

Select multi-

function input

closed

PID SFS

Cancel multi-
function input

closed

+

+

z

-1

+

-

B5-05

PID D Time

B5-01 = 1,3

B5-01 =

1,3

B5-01 = 2,4

+

Upper Limit:

B5-06

PID Limit

+

-

PID Delay

Time

1

B5-08

+

+

z

-1

B5-10

PID Output Gain

B5-01 = 3,4

B5-01 =

1,2

Fmax x 110%

Fmax x 110%

-Fmax x 110%

Frequency
Reference

FWD or REV Jog multi-function input closed

PID Disable multi-function input closed

True

+

+

False

B5-01 = 0

True

False

B5-11 = 0

B5-11 = 1

B5-07

PID Offset

+

+

B5-09 = 0

B5-09 = 1

U1-24

PID Feedback

U1-38

PID Setpoint

-1

U1-36

PID Input

U1-37

PID Output

Frequency Reference

PID Setpoint

PID Feedback

Advertising