Programming 172, Table a.1 f7 parameter list (continued) – Yaskawa F7 Drive Programming Manual User Manual

Page 180

Advertising
background image

Programming 172

H1-03

Multi-Function Digital Input
Terminal S5 Function
Selection
Terminal S5 Sel

15: Fast-Stop N.O.
Closed = Drive decelerates using C1-09, regardless of run

command status.

16: Motor 2 Selection
Closed = Motor 2 (E3-

, E4-

)

Open = Motor 1 (A1-02, E1-

, E2-

)

17: Fast-Stop N.C.
Closed = Normal operation
Open = Drive decelerates using C1-09, regardless of run

command status.

18: Timer Function
Input for independent timer, controlled by b4-01 and b4-02.
Used in conjunction with the multi-function digital output

function H2-

= 12 “timer output”.

19: PID Disable
Closed = Turns off the PID controller.
1A: Accel / Decel Time Selection 2
Based on status of Accel/Decel Time Selection 1 and 2.
1B: Program Lockout
Closed = All parameter settings can be changed.
Open = Only using monitor U1-01 can be changed.
1C: Trim Control Increase
Closed = Increase frequency reference by value in d4-02.
Open = Return to normal frequency reference.
Not effective when Preset References are selected (Multi-step

speed digital inputs are closed). Must be used in conjunction
with Trim Ctrl Decrease.

1D: Trim Control Decrease
Closed = Decrease frequency reference by value in d4-02
Open = Return to normal frequency reference.
Not effective when Preset References are selected (Multi-step

speed digital inputs are closed). Must be used in conjunction
with Trim Ctrl Increase.

1E: Reference Sample Hold
Analog frequency reference is sampled then held at time of

input closure.

20: External Fault, Normally Open, Always Detected, Ramp To

Stop

21: External Fault, Normally Closed, Always Detected, Ramp To

Stop

22: External Fault, Normally Open, During Run, Ramp To Stop
23: External Fault, Normally Closed, During Run, Ramp To Stop
24: External Fault, Normally Open, Always Detected, Coast To

Stop

25: External Fault, Normally Closed, Always Detected, Coast To

Stop

26: External Fault, Normally Open, During Run, Coast To Stop
27: External Fault, Normally Closed, During Run, Coast To Stop
28: External Fault, Normally Open, Always Detected, Fast-Stop
29: External Fault, Normally Closed, Always Detected, Fast-Stop
2A:External Fault, Normally Open, During Run, Fast-Stop
2B:External Fault, Normally Closed, During Run, Fast-Stop
2C:External Fault, Normally Open, Always Detected, Alarm Only
2D:External Fault, Normally Closed, Always Detected, Alarm

Only

2E: External Fault, Normally Open, During Run, Alarm Only
2F: External Fault, Normally Closed, During Run, Alarm Only

(Continued on following page).

0 to 78

3:

2-wire

0:

3-wire

A

A

A

A

H1-04

Multi-Function Digital Input
Terminal S6 Function
Selection
Terminal S6 Sel

0 to 78

4:

2-wire

3:

3-wire

A

A

A

A

Denotes that parameter can be changed when the Drive is running.

Table A.1 F7 Parameter List (Continued)

Parameter

No.

Parameter Name

Digital Operator Display

Description

Setting

Range

Factory

Setting

Control Method

V/F

V/F

w/

PG

Open

Loop

Vector

Flux

Vector